Locating Individual Wires in a Bundle (Energized and
Unenergized Lines)
1.
Attach alligator clip cord set to the T-4000.
2.
Verify that the voltage on the line does not exceed the T-4000
rating.
3.
Connect one alligator clip to the wire you wish to identify and the
other to a separate ground using the 25' ground test lead.
4.
Turn the R-4000CON ON and select 'Low" sensitivity.
5.
Set mode to "SHORT".
6.
At the bundle, pull each individual wire away from the other wires
as far as possible.
7.
Use the R-4000CON to detect the proper wire.
8.
The strongest signal indicates the proper wire (Refer to Figure 18)

Locating outlets From The Breakers Panel

1.
Connect the A2202 Clamp-on to the T-4000 Transmitter and then
clamp it around the conductor.
2.
Set the T-4000 to 'HIGH' signal level.
3.
Set the R-4000CON to 'OPEN' mode and 'LOW' sensitivity.
4.
Hold the R-4000CON in front of each suspected outlet or piece of
equipment. If it is on the same wire as the clamp, the R-4000CON
will indicate it.
5.
If a known outlet does not produce a signal, use the B2024 to boost
the signal. (Refer to Figure 19)
Note: When using the battery booster (B2024 or B2025) the unit will
work in ultra high "U-HI" mode only. Remove the battery booster to
return to normal operation.

Locating Buried Conduit or Metal Pipe

1.
Connect the A2202 clamp-on to the T-4000 Transmitter and then
clamp it around the conduit or pipe.