Relay Status - U-Line U-3045WCINT-60B User Manual & Service Manual

45cm single zone wine cellar
Hide thumbs Also See for U-3045WCINT-60B:
Table of Contents

Advertisement

USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
ID
Description
Amb
Ambient
Thrm
thermistor circuit
Short
shorted.
Temp Hi
Zone temperature
6H+
+10°F over set
point for over 6
hours.
Temp Hi
Zone temperature
12H+
+10°F over set
point for over 12
hours.
Temp Lo
Zone temperature
6H+
-10°F under set
point for over 6
hours.
Temp Lo
Zone temperature
12H+
-10°F under set
point for over 12
hours.
Door
Door switch open
Open 5M
for more then 5
minutes.
To access All Errors follow the steps below.
1. Press
to select "All Errors".
2. Press
.
3. Press
and
to scroll through available
information.
To clear the error log press
press
to confirm.
To exit the Actual Temps menu press
to Menu" and press
to confirm.
Solution
Check thermistor connection to
harness for moisture or
corrosion. Also check connection
where thermistor harness
attaches to main board. If
connections are valid replace
the thermistor.
Is condenser coil clean? Is
condenser fan operating? Check
zone thermistor for correct
resistance. Verify thermistor
connections are clean and
intact. Check zone valve
operation. Sealed system issue?
Is condenser coil clean? Is
condenser fan operating? Check
zone thermistor for correct
resistance. Verify thermistor
connections are clean and
intact. Check zone valve
operation. Sealed system issue?
Verify thermistor connections
are clean and dry. Verify
thermistor resistance. Verify
correct operation of zone valve.
Verify thermistor connections
are clean and dry. Verify
thermistor resistance. Verify
correct operation of zone valve.
Check door switch magnet reed
switch alignment when door is in
closed position. Check reed
switch connection at the harness
and the main board.
to select "Clear Errors" and
to select "Return

Relay Status

Up
Down
Relay status displays the current state of each relay. While
all available relays are displayed, only a portion are used.
ID
Description
Mull
Mullion Heater
Cond
Condenser Fan
Def
Defrost Valve
Pan
Pan heater
Comp
Compressor
NOTE: The Cond (Condenser Fan) will switch state with
the compressor relay, however the condenser fan is
actually powered through a DC output. Condenser fan
status can be viewed through the "Output" service menu
option.
To access Relay Status
1. Use
to select "Relay Status".
2. Press
.
3. Press
and
to scroll through available
information.
To exit the Relay Status simply press
68
u-line.com
Select
RETURN TO MENU
RELAY STATUS
MULL COND DEF
LVLV
OFF
OFF
OFF
OFF
Availability
Not Used
Not Used
Not Used
Not Used
Used
to exit.
Control Operation - Service 3