Venting Installation - Superior Fireplaces WRT6036IS Installation And Operation Instruction Manual

Indoor wood burning fireplace
Table of Contents

Advertisement

OPTIONAL OUTSIDE AIR KIT (MODEL AK4/AK4F)
The installation of an outside air kit should be performed during
the rough framing of the fireplace due to the nature of it's location.
Outside combustion air is accessed through a vented crawl space
(AK4F) or through a sidewall (AK4).
CAUTION: Combustion air inlet ducts shall not
terminate in attic space.
The maximum height for the air vent can not exceed
3 feet below the flue gas outlet of the termination.
Secure to Collars with Metal Tape, Screws or
Straps (Min. of 1/4" x 20" in size)
Vented
Crawl Space
(Check Local
Codes Before
Installing in a
Vented Crawl
Space)
Figure 8 - Outside Air Kit
CHIMNEY PIPE
WARNING: Label part number 900599-01 must
be applied by the installer to all chimney pipe
sections but is not required on sections that will
be visible after the installation is complete. Label
must wrap around the circumference of the pipe.
See accessories, page 28 for Kit F2659.
The IHP chimney system consists of 12", 18", 24", 36" and 48" snap-
lock, double-wall pipe segments, planned for maximum adaptability
to individual site requirements. Actual lengths gained after fitting
overlaps must be taken into consideration (lineal gain) and are
given in the lineal gain chart (see Figure 9). Lineal Gain is the actual
measurable length of a part after two or more parts are connected.
For Canada, use chimney parts designated "HT".
WARNING: The opening in the collar around the
chimney at the top of the fireplace must not be ob-
structed. Never use blown insulation to fill the chimney
enclosure.
126595-01_H

VENTING INSTALLATION

Vent Hood
Air Inlet
Required
Location
for Wall
Must Allow
Installation
For Bushes
or Snow
Air Inlet
Eyebrow
SuperiorFireplaces.us.com
LINEAL GAIN
PART NO.
DESCRIPTION
Signature
Fireplace
12-12DM
Pipe Section
12-12HT
18-12DM
Pipe Section
18-12HT
24-12DM
Pipe Section
24-12HT
36-12DM
Pipe Section
36-12HT
48-12DM
Pipe Section
48-12HT
RLT-12D
Round Termina-
RLT-12HT
Square Chase-
STL-12D
Top with Slip
Section
* The lineal gain for the terminations is measured to the flue gas outlet
height.
15" Galvanized
Outer Pipe
12
/
"
3
8
Stainless
Inner Pipe
Figure 9 - Lineal Gain
ASSEMBLY AND INSTALLATION OF DOUBLE WALL CHIMNEY
SYSTEM
Each double wall chimney section consists of a galvanized outer pipe,
a stainless steel inner flue pipe and a wire spacer. The pipe sections
must be assembled independently as the chimney is installed. When
connecting chimney directly to the fireplace, the inner flue pipe section
must be installed first with the lanced side up. The outer pipe section
can then be installed over 5 the flue pipe section with the hemmed
end up. Press down on each pipe section until the lances securely
engage the hem on the fireplace starter. The wire will assure the proper
spacing between the inner and outer pipe sections.
Continue to assemble chimney sections as outlined above, making
sure that both the inner and outer pipe sections are locked together.
When installing double wall snap-lock chimney together, it is impor-
tant to assure the joint between the chimney sections is locked. Check
by pulling chimney upward after locking. The chimney will not come
apart if properly locked. It is not necessary to add screws to keep the
chimney together (exception, see Figure 10, page 10).
The height of a vertical chimney pipe supported ONLY by the fire-
place, must not exceed 20 feet. Chimney heights above 20 feet must
be supported.
GAIN
66
/
" (1690 mm)
1
2
10
/
" (270 mm)
5
8
16
/
" (423 mm)
5
8
23
/
" (600 mm)
5
8
34
/
" (880 mm)
5
8
46
/
" (1185 mm)
5
8
" * (197 mm)
7
/
3
4
tion
7" (178 mm) to
15"* (381 mm)
Hemmed
End
9

Advertisement

Table of Contents
loading

Table of Contents