Hoshizaki SRK-8H Instruction Manual page 10

Modular crescent cuber
Hide thumbs Also See for SRK-8H:
Table of Contents

Advertisement

2. Remote Condensing Unit
• The remote condensing unit is intended for outdoor use. Normal operating ambient
temperature must be within -20°F to 122°F (-29°C to 50°C). Operation of the
remote condensing unit, for extended periods, outside of this normal temperature
range may affect performance.
• The maximum line set length is 66' (20 m). No refrigerant charge adjustment is
necessary.
• The maximum vertical distance between the remote condensing unit and icemaker
is 33' (10 m) above or 10' (3 m) below the icemaker. These distances are measured
fitting to fitting. See Fig. 1.
• If the vertical distance between the remote condensing unit and the icemaker
is greater than 20' (6 m) (not to exceed 33' (10 m)), an "S" oil-trap (5/8" OD
copper tubing) must be installed in the suction line. The "S" oil-trap must be
located halfway between the icemaker and remote condensing unit. This ensures
sufficient oil return to the compressor.
The remote condensing unit must be positioned in a permanent site under the following
guidelines:
• A firm and flat site.
• A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for proper
air circulation and ease of maintenance and/or service should they be required. See Fig. 2.
Remote
Condensing Unit
(with compressor)
Icemaker
Service Loop
Ice Storage Bin
Suction Line
"S" Oil-Trap
Bin
Min. 24" (61 cm) Clearance
24"
(61 cm)
Air
NOTICE
Icemaker
Max.
16.5
Ice
Feet
Max.
Storage
33
Bin
Feet
Max.
16.5
Feet
Remote
Condensing Unit
(with compressor)
Fig. 1
24"
(61 cm)
Air
Fig. 2
10
Max.
Service Loop
10
Feet