Status Indicator; Communications-Related Parameters - Toshiba PDP002Z Function Manual

Profibus-dp option
Table of Contents

Advertisement

2.4. Status indicator

The PDP002Z has two LEDs, ST (status) and DX (data exchange) to indicate the
statuses of PROFIBUS-DP and the PDP002Z itself.
ST (Status): Red LED
Flashes
ST
Lights
DX
MNS
MNS
DX (Data exchange): Green LED.
MNS
Indicates the status of the PROFIBUS network.
It lights when the PDP002Z is on-line and data exchange is possible.

2.5. Communications-related parameters

Parameter
Function
Communication
f830*
option setting 1
(PPO TYPE)
Communication option
f831
setting 2 - 13
-
f846
Inverter operation at
f851
the communications
loss action
(Network wire breaks)
Preset speed
f852
operation selection
Monitoring of
f853
communication
device station
address
Monitoring of
f854**
communications
device's baud rate
* When the parameters are changed, the power must be cycled to the VF-AS1/PS1 for
the changes to take effect.
** The baud rate of the PDP002Z is automatically set by configuration a baud rate for the
master.
LED
Off
No diagnostics present
Waiting for parameterisation or configuration
DP status error
* For example, a station address is not setcorrectly.
0: None
1: PPO TYPE 1
2: PPO TYPE 2
3: PPO TYPE 3
4: PPO TYPE 4
Refer to section 4.
0: Stop and break of connection
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation
frequency set with f852)
0: None
1 to 15: Preset speed
Displays the station address assigned with the
DIP switch.
0 to 125
Displays the network communication speed set
with the DIP switch.
0:
1:
2:
3:
1.5 Mbit/s
4:
500 kbit/s
5:
187.5 kbit/s
6:
93.75 kbit/s
7:
45.45 kbit/s
8:
19.2 kbit/s
9:
255:
Meanings
Adjustment range
12 Mbit/s
6 Mbit/s
3 Mbit/s
9.6 kbit/s
Disabled
- 7 -
E6581343 ③
Default setting
0
0
0
0
2