4.1. How to use
The purposes are adjustment by real time command transmission, and the monitor of an
operation state by using cyclic communication of PROFIBUS.
Example 1: Command transmitting
When you want to set "0xC400" to parameter fa06, set "1 (FA06)" to parameter
f831.
And Since 0 and 1 byte of the PZD1 supports the parameter f831, if "0xC400" is set
up here, "0xC400" will be set as fa06.
VF-AS1/PS1
Parameter
1 (FA06)
f831
f832
f833
...
"C400" is set as parameter fa06
Example 2: State monitoring
When you want to monitor the output current, set "3 (FD03)" to parameter f841.
The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the
parameter f841 is inputted.
VF-AS1/PS1
Parameter
f841
3 (FD03)
f842
f843
...
The value of a parameter fd03 is outputted.
Value
...
...
...
Value
...
...
...
PDP002Z
PDP002Z
- 20 -
E6581343 ③
PROFIBUS Master
PZD1
PZD2
C4
00
...
...
PROFIBUS Master
PZD1
PZD2
xx
xx
...
...
PZD3
...
...
PZD3
...
...