Remove The Front Panel; Installation Of Plumbing - Rinnai V Model Series Installation And Operation Manual

Outdoor tankless water heater
Table of Contents

Advertisement

Remove the Front Panel

Slide the plastic trim pieces on each side of the
water heater to expose the screws.
Remove the 4 screws and pull off the front panel.

Installation of Plumbing

Pressure Relief Valve Requirements
Install the pressure relief valve according to local
plumbing codes and these instructions.
An approved pressure relief valve is required by the
American National Standard (ANSI Z21.10.3) for all
water heating systems, and shall be accessible for
servicing.
DO NOT
Do not plug the relief valve and do not install any
reducing fittings or other restrictions in the relief
line. The relief line should allow for complete
drainage of the valve and the line.
Do not place any other type valve or shut off
device between the relief valve and the water
heater.
MUST DO
The relief valve must comply with the standard for
Relief Valves and Automatic Gas Shutoff Devices for
Hot Water Supply Systems ANSI Z21.22 and /or the
standard Temperature, Pressure, Temperature and
Pressure Relief Valves and Vacuum Relief Valves,
CAN1-4.4.
The relief valve must be rated up to 150 psi and to
at least the maximum BTU/hr of the appliance.
The discharge from the pressure relief valve should
be piped to the ground or into a drain system to
prevent exposure or possible burn hazards to
humans or other plant or animal life. Follow local
codes. Water discharged from the relief valve
could cause severe burns instantly, scalds, or
death.
The pressure relief valve must be manually
operated once a year to check for correct
operation.
The relief valve should be added to the hot water
outlet line and near the hot water outlet according
to the manufacturer's instructions. DO NOT place
any other type valve or shut off device between
the relief valve and the water heater.
INFORMATION
If a relief valve discharges periodically, this may be
due to thermal expansion in a closed water supply
system. Contact the water supplier or local
plumbing inspector on how to correct this
situation. Do not plug the relief valve.
The American National Standard (ANSI Z21.10.3)
does not require a combination temperature and
pressure relief valve for this appliance. However,
local codes may require a combination
temperature and pressure relief valve.
Isolation Valves
Rinnai strongly recommends the installation of
isolation valves on the cold and hot water lines
because they provide the ability to isolate the water
heater from the structure's plumbing and allow quick
access to flush the heat exchanger. Flushing the heat
exchanger regularly is required as part of the proper
maintenance for this water heater.
Piping Requirements
A manual water control valve must be placed in the
water inlet connection to the water heater before it is
connected to the water line. Unions may be used on
both the hot and cold water lines for future servicing
and disconnection of the unit.
DO NOT
Do not introduce toxic chemicals such as those
used for boiler water treatment to the potable
water used for space heating.
MUST DO
The piping (including soldering materials) and
components connected to this appliance must be
approved for use in potable water systems.
Purge the water line to remove all debris and air.
Debris will damage the water heater.
If the appliance will be used as a potable water
source, it must not be connected to a system that
was previously used with a non-potable water
heating appliance.
Ensure that the water filter on the water heater is
clean and installed.
V53De Manual
9