AERATION
ADJUSTMENT
Theairshuttercanbeadjustedbymovingtheadjust-
ingwireupordown.Thewireisaccessedthrough
thebottom.Opentheairshutterforablueflame
orcloseforayellowerflame.Theburneraeration
isfactorysetbutmayneedadjustingduetoeither
thelocalgassupplyoraltitude.
Minimum Air Shutter Opening:
3/16"
Natural Gas
1/4"
Propane
CAUTION: Carbon will be produced if air shutter
is closed too much.
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
Note: Aeration Adjustment should only be
performed by an authorized FPI Installer
at the time of installation or service.
1. Removeone(1)screwontherightsideofthe
unittoremovetheaccesspanel.
Pull adjustment wire up to close or
down to open aeration
Closed - Tall yellow
Open - Short Blue
GAS PIPE
PRESSURE TESTING
Theappliancemustbeisolatedfromthegassup-
plypipingsystembyclosingitsindividualmanual
shut-offvalveduringanypressuretestingofthegas
supplypipingsystemattestpressuresequaltoor
lessthan1/2psig.(3.45kPa).Disconnectpiping
fromvalveatpressuresover1/2psig.
Themanifoldpressureiscontrolledbyaregulator
builtintothegascontrol,andshouldbechecked
atthepressuretestpoint.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Makesuretheunitisinthe"OFF"position.
2) Loosenthe"IN"and/or"OUT"pressuretap(s),
turningcounterclockwisewitha1/8"wideflat
screwdriver.
3) Attachmanometerto"IN"and/or"OUT"pressure
tap(s)usinga5/16"IDhose.
4) Lightthepilotandturnthevalveto"ON"posi-
tion.Readmanometer.
5) Thepressurecheckshouldbecarriedoutwith
theunitburningandthesettingshouldbewithin
thelimitsspecifiedonthesafetylabel.
6) Whenfinishedreadingmanometer,turnoffthe
gasvalve,disconnectthehoseandtightenthe
screw(clockwise)witha1/8"flatscrewdriver.
Note: Screw should be snug, but do not over
tighten
885 S.I.T. VALVE
DESCRIPTION
1) 6Stageflameadjustment
2) Pilotadjustment
3) InletPressureTap
4) OutletPressureTap
5) PilotOutlet
6) MainGasOutlet
7) MainGasInlet
4
3
4
3
5
5
6
6
Hampton®H15E-11DirectVentFreestandingGasStove
installation
2
2
1
1
7
7
|