Aeration Adjustment; Gas Pipe Pressure Testing; I.t. Valve Description - HAMPTON BAY H35E-11 Owners & Installation Manual

Direct vent gas fireplace
Table of Contents

Advertisement

installation
Aeration
Adjustment
The air shutter can be adjusted by moving the adjust-
ing wire up or down. The wire is accessed through
the bottom. Open the air shutter for a blue flame or
close for a yellower flame. The burner aeration is
factory set but may need adjusting due to either the
local gas supply or altitude.
Natural Gas
1/4" (6.4 mm)
Propane
3/8" (9.5 mm)
1. Loosen the 2 screws on the bottom cover and
take out the one on the left side (when facing
the back of the unit).
Remove this screw
Remove this screw
Location of the Aeration Adjustment wire
Location of the Aeration Adjustment wire
Pull adjustment wire up to close or down to open
aeration.
Caution: Carbon will be produced if the air
shutter is closed too much.
Note: Any damage due to carboning re-
sulting from improperly setting the
aeration controls is NOT covered
under warranty.
Note: Aeration Adjustment should only
be performed by an authorized FPI
Installer at the time of installation
or service.
|
40
Hampton
H35E-11 Direct Vent Freestanding Gas Stove
®
Gas Pipe
Pressure Testing
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide flat
screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Turn the unit on with the remote and note the
pressure reading.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6) When finished reading manometer, turn off
the unit, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but not over
tightened.
885 S.I.T. Valve
Description
1) 6 Stage flame adjustment
2) Pilot adjustment
3) Inlet Pressure Tap
4) Outlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
4
3
4
3
2
2
1
1
5
5
6
6
7
7