Table 2: Installer Configuration Menu (Part 2 of 5)
Parameter
Description and Default
Appearing
on Display
DI2
Configuration of Digital Input 2.
Default: None
Lockout
Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
1
Sets the delay time period at
Pwr del
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
Frost pr
Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default: off
2
Sets the Occupied and Unoccupied
Heat max
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
2
Sets the Occupied and Unoccupied
Cool min
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default: 2.0 min
TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions
Selection Options
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning
unit control card, which provides an alarm should there be a
malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
Function
Resume/Occupancy
Access
Override Scheduling
Permanent
Access
Temperature
Setpoints
Temporary
Access
Temperature
Setpoints
System Mode Setting
Access
Fan Mode Setting
Access
Range: 10.0 to 120.0 sec
(on): Enabled
(off): Disabled
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Level
(0)
(1)
Access
No Access
No Access
No Access
Access
No Access
No Access
No Access
No Access
No Access
(2)
9

Advertisement

Table of Contents