Johnson Controls TEC2104-3 Installation Instructions Manual page 5

N2 networked multi-stage economizer thermostat
Table of Contents

Advertisement

Table 1: N2 Bus Objects (Part 1 of 2)
Point Name
1
Room Temp
Aux Temp/Outdoor Temp
1,2
Heating SP
(Occupied Heating SP)
1,2
Cooling SP
(Occupied Cooling SP)
1,2
Setback Heating SP
(Unoccupied Heating SP)
1,2
Setback Cooling SP
(Unoccupied Cooling SP)
Minimum Heat SP
1
Maximum Heat SP
1
Minimum Cool SP
Maximum Cool SP
Mixed Air/Discharge Air
Temperature (MS)
1
Fan
1
Mode
1
Occupancy
W1 State
W2 State
Y1 State
Y2 State
G State - Fan
1,5
Temp Units
(Local Display Only)
Occupancy Override
Temporary Occupancy
1,3
Time
6,7
DI1
TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions
TEC Point
N30/NAE
Type/Address
Object Type
ADI-1
N2 AI
1
ADI-2
N2 AI
ADI-3
N2 AO
ADI-4
N2 AO
ADI-5
N2 AO
ADI-6
N2 AO
ADI-7
N2 AI
ADI-8
N2 AO
ADI-9
N2 AO
ADI-10
N2 AI
ADI-11
N2 AI
BD-1
N2 BO
BD-2
N2 MSO
BD-3
N2 BO
BD-4
N2 BI
BD-5
N2 BI
BD-6
N2 BI
BD-7
N2 BI
BD-8
N2 BI
BD-9
N2 BO
BD-10
N2 BI
BD-11
N2-MSO
BI-1
N2 BI
BAS Model
Point Type
CSAD
CSAD
CSAD
CSAD
CSAD
CSAD
CSAD
CSAD
CSAD
CSAD
CSAD
CSBD
3,4
CSMS
CSBD
CSBD
CSBD
CSBD
CSBD
CSBD
See Footnote 5.
CSBD
CSMS
CSBI
Override Range
32 to 122°F (0 to 50°C)
-40 to 122°F (-40 to 50°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
40°F (4.5°C)
40 to 90°F (4.5 to 32°C)
54 to 100°F (12 to 37.5°C)
100°F (37.5°C)
-40 to 122°F (-40 to 50°C)
0 = Auto
1 = On
0 = Off
1 = Cool
2 = Heat
3 = Auto
0 = Unoccupied
1 = Occupied
0 = Off
1 = On
0 = Off
1 = On
0 = Off
1 = On
0 = Off
1 = On
0 = Off
1 = On
0 = °C
1 = °F
0 = No Override
1 = Override
0 = 0 hours
1 = 1 hour
2 = 2 hours
.
.
12 = 12 hours
0 = Off
1 = On
5

Advertisement

Table of Contents
loading