Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter
Description and Default
Appearing
on Display
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Fan cont
Determines how the fan is activated
in response to a call for heating.
Fan cont applies to W1 and W2 and
Fan Mode auto only. Fan cont does
not affect fan operation on a call for
cooling (Y1 and Y2).
Default: on
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
Com addr
N2 network address at the
thermostat; coincides with the
address assigned at the supervisory
controller.
Default: 4
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default: 3.0 hrs
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
10
TEC2104-3 N2 Networked Multi-Stage Economizer Thermostat Installation Instructions
Selection Options
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
(off): The thermostat does not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on): Enables the thermostat to control the fan.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Range: 1 to 255
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments