Siemens LMV36.520 Series Manual page 26

Basic unit with integrated fuel-air ratio control for forced draft burners

Advertisement

Technical Data (cont´d)
Dual fuel switch unit
AGM60
Terminal output Inputs
26/30
Smart Infrastructure
Mains voltage
Mains frequency
Power consumption
Safety class
Galvanic separation between mains
voltage terminals and actuator signal lines
and actuator supply lines
Degree of protection
Detection time fuel changeover
Switching frequency fuel changeover
Switching cycles fuel changeover
Permissible primary fuse (Si) (external)
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
terminals, the AGM60 must be replaced.
Mains supply:
Input current depending on the operating state of the LMV36
Mains voltage is monitored by the burner control
Dimensions (W x H x D)
Mounting
Status input: Fuel selection, pressure switch
Input currents and input voltages
- UeMax
- UeMin
- IeMax
- IeMin
Contact material recommendation for
external switching contact,
transducer (pressure switch-max,
POC)
Transition / settling behavior / bounce
- Perm. bounce time of contacts
when switching on/off
UN
Voltage detection
- On
- Off
AC 120 V -15% / +10%
50/60 Hz ±6%
<5 W (typically) (without actuator supply)
I with parts according to II and III to
EN 60730-1:2016
No
IP00 according to EN 60529:1991 +
A1:2000 + A2:2013
Note:
The burner or boiler manufacturer (OEM)
must ensure degree of protection IP40 to
EN 60529:1991 + A1:2000 + A2:2013 for
burner controls by adequate installation of
the AGM60...
The AGM60 together with the LMV36 is
suited for installation under the burner
hood or inside a control cabinet or control
panel
<400 ms
Min. 3 s
Max. 5´000
Max. 6.3 AT
Power must always be supplied via the
LMV36 (refer to chapter Inputs / Outputs)
180.7 x 120.7 x 51.7 mm
Top hat rail to DIN EN 60715,
35 mm or screwed
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
Gold-plated silver contacts
Max. 50 ms (after the bounce time, the
contact must stay closed or open)
AC 120 V
AC 90...132 V
<AC 40 V
CC1N7544en