Technical Data (cont´d)
Terminal loading
«Outputs»
Analog output / load
output X74 pin 3
18/30
Smart Infrastructure
Total contact loading:
Rated voltage
Unit input current (safety loop) from:
- Fan motor contactor
- Ignition transformer
- Fuel valves
- Oil pump / magnetic clutch
(optional via AGM60)
Individual contact loading:
Fan motor contactor
Rated voltage
Rated current
Power factor
Alarm output
Rated voltage
Rated current
Power factor
Ignition transformer
Rated voltage
Rated current
Power factor
Fuel valves
Rated voltage
Rated current
Power factor
Operation display
Rated voltage
Rated current
Power factor
Safety valve (magnetic clutch / oil pump)
Rated voltage
Rated current
Power factor
Connections for pressure switch
Rated voltage
Rated current
Power factor
Power supply for pressure switch -max / POC (X5-02 pin 3 or X22-02 pin 3)
IaMax
Fuel feedback to LMV36 (X31-02 pin 1 or X31-02 pin 2)
IaMax
Accuracy of output voltage
AC 120 V, 50 / 60 Hz
Max. 5 A
AC 120 V, 50 / 60 Hz
1.6 A pilot duty output declaration to
UL372
Cos >0.4
AC 120 V, 50 / 60 Hz
1 A
Cos >0.4
AC 120 V, 50 / 60 Hz
1.6 A pilot duty output declaration to
UL372
or
250 VA ignition output declaration to
UL372
Cos >0.2
AC 120 V, 50 / 60 Hz
1.6 A pilot duty output declaration to
UL372
Cos >0.4
AC 120 V, 50 / 60 Hz
0,5 A
Cos >0.4
AC 120 V, 50 / 60 Hz
1.6 A pilot duty output declaration to
UL372
Cos >0.4
AC 120 V, 50 / 60 Hz
1.5 mA
---
<10 mA
<10 mA
±1 %
CC1N7544en