Technical Data (cont´d)
Cable lengths
Cross-sectional areas
Connections of
actuators
AGV50 signal cable
AZL2  BCI
Smart Infrastructure
Mains line AC 120 V
Display, BCI
Load controller X5-03
Load controller analog X64 (24 mA)
Safety loop / burner flange (total)
External lockout reset button
Safety valve
Load output ¹)
VSD control ¹)²)
Speed input
Fuel valve (V1 / V2 / V3)
Pilot valve
Ignition transformer
Other lines
¹) Do not run the cable together with other cables. If not observed, hum voltage might
cause electromagnetic interference
²) Shorter cable length due to closed control loop
Specification as per EN 60730-1:2016
Type of shutdown or interruption of each circuit
Shutdown with microswitch
Mode of operation
The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, the
safety loop (safety limit thermostat, water shortage, etc.) must be sized for rated
currents according to the selected external primary fuse. The cross-sectional areas of
the other cables must be sized in accordance with the internal unit fuse (max. 6.3 AT).
Min. cross-sectional area
Cable insulation must meet the relevant temperature requirements and environmental
conditions.
Fuses (F1) used inside the LMV36
The fixed connected actuator cables must not be extended.
Signal cable
Cable length
- AGV50.100
- AGV50.300
Location
Max. 100 m (100 pF/m)
For installation under the burner hood or
in the control panel
Max. 3 m (100 pF/m)
Max. 20 m (100 pF/m)
Max. 20 m (100 pF/m)
Max. 20 m (100 pF/m)
Max. 20 m (100 pF/m)
Max. 20 m (100 pF/m)
Max. 10 m (100 pF/m)
Max. 3 m (100 pF/m)
Max. 3 m (100 pF/m)
Max. 3 m (100 pF/m)
Max. 3 m (100 pF/m)
Max. 3 m (100 pF/m)
Max. 3 m (100 pF/m)
1-pole
Type 2 B
0.75 mm² (single- or multi-core as per
VDE 0100)
6.3 AT (IEC 60127 2:2014)
Color white
Unshielded
Conductor 4 x 0.141 mm²
With RJ11-plug
1 m
3 m
Under the burner hood (extra measures
required for SK II EN 60730-1:2016)
19/30
CC1N7544en
21.05.2021