Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
Each control unit 5000-5001 has the following basic configuration:
Grey metal cabinet
MMI board (5011) (not in 5001)
 EBL512 G3 front with display (not in 5001)
Main board (5010)
 Space & connectors for two TLON connection boards
(1590/5090). NOTE! In EBL512 G3 United version 2.7.x
can only one TLON connection board be used (Network 0).
 Four COM loops (0-3) to which the loop units are connected.
 Four programmable supervised voltage outputs (S0-S3).
 Two programmable relay outputs (R0-R1).
 Four programmable inputs (I0-I3).
 Six 24 V DC outputs (power supply outputs for Web-server II
(1598),
routing
Connections and more information, see dwg. 512 G3 - 22.
 Two not programmable relay outputs for routing equipment
(Fire alarm output for Fire brigade tx and Fault condition
output for Fault tx). Connections and more information, see
dwg. 512 G3 - 24.
 Battery charger.
Built-in power supply. See chapter "Power supply", page 152.
Connections and more information, see dwg. 512 G3 - 21.
 Switched power supply (rectifier), 230 V AC / 24 V DC
(5037).
 Space and connection cables for two Sealed Lead-Acid backup
batteries (12 V, 28 Ah).
Space for up to six expansion boards (458x).
See following chapters for more and detailed information.

Mounting plates

The 5000 and 5001 units are delivered with a mounting plate
approved for mounting on an incombustible wall (e.g. concrete).

Mounting plate for 19" mounting rack, 5020

When the 5000 and 5001 units shall be mounted in a 19" mounting
rack, the standard mounting plate can be replaced with a Mounting
plate for 19" mounting rack 5020.

Mounting plate for inflammable wall, 5021

When the 5000 and 5001 units shall be mounted on an inflammable
wall (e.g. wood), the standard mounting plate should be replaced with
equipment
and
external
22
equipment).