Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
NOTE! If any of these values are changed, it might fasten or
delay the alarm activation.
System information
In this tab you can read the following information:
Logical name
Number of Control units
Number of addresses
Number of expansion cards
When some name is changed, added or removed units, this
information is updated.
Alert Annunciation and Alarm
Acknowledgement Facility
Alert Annunciation
See also chapter "Alert Annunciation", page 97.
Acknowledgement time: 30 sec.
30 is default. 5, 10, 15, - -300 (= 5 min.) is possible.
Investigation time: 3 min.
3 is default. 1-40 is possible
Number of zones: 1
1 is default. 1-4 is possible
Multiple alarms allowed within same zone
If only one alarm point within the zone is allowed to activate alert
annunciation, this checkbox shall be unmarked.
NOTE! According to EN54-2, the total delay of fire alarm routing
equipment (Acknowledge time + Investigation time) must not exceed
10 minutes.
Alarm Acknowledgement Facility
Used in conjunction with the AAF Control, which is available on the
Australian market only.
See also chapter "Alarm Acknowledgement Facility (AAF)", page 99.
Acknowledge period (AP) time: 60 sec.
60 is default. 10-60 is possible.
Investigation period (IP) time: 3 min.
3 is default. 1-3 is possible.
Two zone dependence
See also chapter "2-zone / 2-address dependence (Co-incidence
alarm)", page 94.
Group
Zone: A list box displays all the so far programmed
zones in the system, i.e. the zones have to be programmed in Win512