Configuration Of The Ip Address; Modifiable Parameters For Epxmbe001/Epxmbe101 - Emerson PACSystems RSTi-EP User Manual

Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958L
Specification
Storage temperature
Air humidity (operation/transport)
Width
Depth
Height
Weight
4.4.4

Configuration of the IP Address

The web server can be used to define whether a static IP address shall be used, or the address
shall be assigned automatically (DHCP/BootP).
Network adapters using firmware version 01.xx.xx are preset to the static IP address
192.168.0.222.
Network adapters using firmware version 02.00.00 or higher will by default send a DHCP
discover first. If no assignment by a DHCP server follows during the next 30 seconds, the
static IP address 192.168.0.222 will be set.
4.4.5

Modifiable Parameters for EPXMBE001/EPXMBE101

Parameter
IP-Address
#
Subnet mask
#
Gateway
#
IP Configuration
#
MODBUS DHCP Timeout
Additional TCP port
1
Modbus Dual LAN Mode
(EPXMBE101 only)
IP-Address USB Port†
Webserver via Ethernet
Save module parameters
2
Status Modbus watchdog
Modbus Connection
Timeout
Write access in multi-client
operation
Check reference list before
exchanging data
Process alarm
Diagnostic alarm
Detailed Descriptions of the Fieldbus Network Adapters
Description
-40°C to +85°C (-40 °F to +185 °F)
5% to 95%, noncondensing as per IEC 61131-2
52 mm (2.05 in)
76 mm (2.99 in)
120 mm (4.72 in)
223 g (7.87 oz)
Optional values
4 numbers between 0-255
4 numbers between 0-255
4 numbers between 0-255
Static, DHCP, BootP
Waiting time, 1 to 1,000 s
0 (disabled) / Value from 1 to
65,535
(except for 80 and 161)
disabled / enabled
192.168.1.202; 192.168.2.202,
192.168.3.202, 192.168.4.202,
192.168.5.202
disabled / enabled
no / yes / Standard
Watchdog time in steps of 10ms
Connection watchdog time in sec
write for all, 1stWr1stServe,
1stConn1stServe
disabled / enabled
disabled / enabled
disabled / enabled
Default
192.168.0.222
255.255.255.0
192.168.0.1
DHCP and static
30 s
0
disabled
192.168.1.202
disabled
no, refer to register 0x113C – 0x113F Save
Module Parameters
0 *10ms, refer to register 0x1120 MODBUS
DATA EXCHANGE watchdog, predefined time
1 s, refer to register 0x1131 MODBUS
CONNECTION Timeout in Sec
write for all, refer to register 0x1031 MODBUS
CONNECTION Mode Register
disabled, refer to register 0x1132 Check
Reference List prior to Data Exchange
refer to register 0x1133 Process Alarm
refer to register 0x1134 Diagnostic Alarm
Section 4
May 2021
100