4.6 Remote Operation Function

The remote operation function is provided to control the operation of a C Controller module
or programmable controller CPU from the user program or the C Controller setting utility of
the development environment (personal computer).
Use the bus interface functions to create the user program of the C Controller module.
There are the following three different remote operations.
Remark

4.6.1 Remote RUN/STOP

For the remote RUN/STOP operation from a programmable controller CPU, refer to the
manual for the programmable controller CPU.
(1) Definition of remote RUN/STOP
(2) Application of remote RUN/STOP
(3) Operation for remote RUN/STOP
4
- 72
4.6 Remote Operation Function
4.6.1 Remote RUN/STOP
• Remote RUN/STOP :
• Remote PAUSE
:
• Remote RESET
:
Remote RESET is executable for C Controller modules or CPU No,1
(programmable controller CPU).
Remote RUN/STOP is the operation that sets the C Controller module into the RUN or
STOP status from the user program or development environment (personal
computer), with the RUN/STOP/MODE switch on the C Controller module set to RUN.
Remote RUN/STOP is convenient when:
• The C Controller module is out of reach.
• The C Controller module inside a control panel is to be run or stopped by external
signals.
Execution of remote RUN/STOP makes the C Controller module behave as described
below.
(a) Remote STOP
As soon as a remote STOP request is issued, the module is stopped, and the
output (Y) to each module and writing to buffer memory from the user program are
disabled.
Note that these operations are executable from the <<Module monitoring>> tab of
the C Controller setting utility.
(b) Remote RUN
Executing remote RUN in the STOP status caused by remote STOP changes the
module status to RUN again, enabling the output (Y) to each module and writing
to buffer memory from the user program.