Ds205 Energy Counter; Ds206 Load Profiles - Siemens SENTRON PROFINET Proxy SPP2000 Manual

Hide thumbs Also See for SENTRON PROFINET Proxy SPP2000:
Table of Contents

Advertisement

6.3.11

DS205 energy counter

Via data set DS205, all energy counters of the PAC device that are in Double format can be
read out and only set in the PAC3200T.
This data set only applies to the SENTRON PAC devices. The corresponding slot/subslot
address must therefore be used for reading.
Table 6- 15
Structure of data set DS205 - read access and write access
Byte
Length
(bits)
0
64
8
64
16
64
24
64
32
64
40
64
48
64
56
64
64
64
72
64
max. 80
Note
For writing energy counters, fill all fields of the energy counter that are not to be overwritten
with 0xFFFFFFFFFFFFFFFF.
6.3.12

DS206 load profiles

Via data set DS206, the current measured values of the load profile period of the
SENTRON PAC devices last stored can be read out.
This data set only applies to the SENTRON PAC devices. The corresponding slot/subslot
address must therefore be used for reading.
Table 6- 16
Byte
0
4
8
12
16
20
PROFINET Proxy SPP2000
Equipment Manual, 03/2022, L1V30814715D-01
Format
Description
Double
Active energy import tariff 1
Double
Active energy import tariff 2
Double
Active energy export tariff 1
Double
Active energy export tariff 2
Double
Reactive energy import tariff 1
Double
Reactive energy import tariff 2
Double
Reactive energy export tariff 1
Double
Reactive energy export tariff 2
Double
Apparent energy tariff 1
Double
Apparent energy tariff 2
Structure of data set DS206 - read access only
Number of
bits
32
32
32
32
32
32
PAC2200
PAC2200
MID
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Format
Description
Float
Cumulated active power import
Float
Cumulated reactive power import
Float
Cumulated active power export
Float
Cumulated reactive power export
Float
Maximum value of active power
Float
Minimum value of active power
Data traffic
6.3 Acyclic data traffic
PAC2200
PAC3200T
CLP
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
R
R/W
57

Advertisement

Table of Contents
loading

Table of Contents