Troubleshooting
Troubleshooting
If you have problems mounting, wiring, or addressing the TV-VAVB3-E2, contact Carrier Control Systems Support.
LEDs
Net (Network Status) Tricolor LED
Color
Pattern
On
Red
1 blink
Red
On
Blue
TruVu™ VAVB3-E2
Installation and Start-up Guide
Condition
Ethernet connection problem
One of the following BACnet/IP
(Ethernet) DLL reporting issue:
•
Unable to create tasks
•
Unable to open socket for
BACnet port
One of the following issues:
•
Port communication firmware
did not load properly
•
Port communication firmware
is not running
•
Invalid protocol selected
98
Message in Module
Status
•
No Ethernet Link
•
BACnet/IP error
•
MSTP firmware error
•
CARRIER CORPORATION ©2022
Possible Solutions
Connect Ethernet Cable
Check other network
components
Cycle power
Change protocol using
USB Service Port
Cycle power
All rights reserved