Kidde Scorpio CPD 7051 Series Installation, Operation & Maintenance Manual page 9

Fire control panel

Advertisement

TO MAIN CIRCUIT
120VAC, 0.5A, 50/60 HZ
240VAC, 0.25A, 50/60 HZ
GROUND
0.485A MAX CHARGING CURRENT
SUPERVISED, USE ONLY KIDDE-FENWAL
BATTERY CAT. NO. 06-115915-020
(CONSISTS OF ONLY ONE BATTERY)
24VDC
1.2A-H
FOR CANADIAN SYSTEMS, CONNECT BATTERIES
TO BATTERRY CUTOUT CIRCUIT AS SHOWN ABOVE.
1
ABORT
CIRCUIT
MAX LINE RESISTANCE 50 OHMS
MANUAL
1
RELEASE
CIRCUIT
MAX LINE RESISTANCE 50 OHMS
1
SUPERVISORY
CIRCUIT
MAX LINE RESISTANCE 50 OHMS
DETECTOR 1
1
CIRCUIT
17.3 - 26.0 VDC
MAX LINE RESISTANCE 50 OHMS
DETECTOR 2
1
CIRCUIT
17.3 - 26.0 VDC
MAX LINE RESISTANCE 50 OHMS
INSTALLATION NOTES:
1. End of line resistors are 10K ohm. 1/2 watt. These
resistors are not supplied with panel, but available as
part no. 06-129520-001 (kit of 50).
2. Maximum number of smoke detectors per circuit is
15.
3. Release devices: See Figures 4 and 5 for wiring.
4. The non-supervised aux power supply circuit is only
intended to supply up to 0.25 A to power a single 24
VDC notification appliance when installed in the same
room and with all wiring in conduit.
The connection to this device must include a N.O.
Alarm contact relay closure.
5. The trouble contacts are marked with the panel either
de-energized (no power) or in trouble condition. The
06-235793-001
25VRMS
XFMR
+
BATT
24VDC
1.2A-H
XFMR
+
BATT
MAXIMUM WIRE SIZE #14AWG.
1
2
3
4
5
6
7
8
9 10
11 12
+
+
+
2
WHEN USED MUST
CONNECT TO ALARM1
OR ALARM2 CONTACTS
SEE NOTE 4
2
Figure 3. Installation Wiring Diagram
firealarmresources.com
06-129800-002
S2
ON
1
PWR
SYS
2
ON
TBL
3
ZONE
ZONE
4
1
1
5
ALM
TBL
6
7
ZONE
ZONE
8
2
2
ALM
TBL
RESET
MNL
MNL
REL
REL
ALM
TBL
ABT
ABT
ACT
TBL
SPV
SPV
ON
TBL
REL
SIG
OUT
SIL
SIG SIL
TBL
ISOLATE
ON
13 14 15
16
17
18
19
20
21
22
23
24 25 26
NO
C
NC
NO
C
NC
NO
C
NC
N/CN/C
N/CN/C
ALARM 1
ALARM 2
TROUBLE
CONTACTS RATED AT
2A; 30VDC, 250VAC
TO TERMINAL
TO TERMINAL
15 OR 18
16 OR 19
AUX. PS CIRCUIT
MAX CURRENT 0.25A
MAX STANDBY CURRENT 0mA
MAX RIPPLE 1.5Vpp
relay is energized and the contacts change state on
application of power to the panel. The relay is de-en-
ergized in trouble condition.
6. If there are no devices connected to the release cir-
cuit, connect a 300 ohm, 2 watt resistor between ter-
minals 28 and 31.
7. Circuits marked with a circle (
field wiring must be routed away from ac in and bat-
tery wiring.
8. If using a power limited power source, follow note 7. If
using a non-power limited source, maintain a mini-
mum 1/4" spacing from all power limited wiring.
9. For ULC installations, all extended circuits shall not
exceed 120 V nominal (150 V max to ground).
5
Scorpio
S2 PROGRAM SWITCH
SEE TEXT FOR DEFINITIONS
S4 RELEASE CIRCUIT ISOLATE SWITCH
JUMPERS W1 & W2 MUST BE OUT
TO ALLOW ISOLATE FUNCTION
RESET SWITCH
HOLD FOR 5 SECONDS TO CLEAR ALARM
INDICATES SUPERVISED CIRCUIT
INDICATES POWER LIMITED CIRCUIT
S4
O
F
F
27 28
29 30 31
+
+
+
3
3
RELEASE CIRCUIT
BELL CIRCUIT
1
24VDC
REGULATED
MAX CURRENT 0.5A
24VDC
) are power limited; all
o
December 2001