Installation,
Operation &
Maintenance Manual
December 2001
TM

Advertisement

loading

Summary of Contents for Kidde Scorpio CPD 7051 Series

  • Page 1 December 2001 Scorpio Fire Control Panel Installation, Operation & Maintenance Manual P/N 06-235793-001 UL Listing File No. S2422 Fire Systems firealarmresources.com...
  • Page 2 firealarmresources.com...
  • Page 3: Safety Summary

    SAFETY SUMMARY Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: Warning - Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or intercon- necting cables while the unit is energized.
  • Page 4: General Safety Notices

    Auxiliary Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled.
  • Page 5 Engineered suppression systems. The release circuit provides increased reliability. The control unit is compat- will activate two 24 Vdc control heads (Kidde P/N ® ible with KIDDE FM-200 , FE-13™, CO , Industrial Dry 48650001, 899175 or 890181).
  • Page 6 Scorpio ™ ABORT FUNCTION 1. Hold the RESET Switch down. All LEDs should light The control panel incorporates a fully supervised style “B” 2. Release the RESET Switch. All LEDs should return to abort circuit which will monitor N.O. contact devices. The Normal.
  • Page 7 Scorpio ™ interface switches and indicators are located on the op- Table 3. Switch Settings erator interface board behind the locked cover. The en- closure is of sufficient size to house the two 1.2 V 1.2 AH batteries required for standby power operation. An optional dead-front enclosure (P/N 06-235500-001) is available (mandatory for use in Canada).
  • Page 8 Scorpio ™ lease time delay. Abort sequence is dependent upon WIRE SIZES programming. AC power feed: #14 minimum (#12 Max.) Alarm Condition - Panel Programmed for Two Zone All Others: #14, 16 or 18 Mode BATTERY POWER Upon receipt of an alarm from one activated detector in one zone: Batteries provide 24 hour standby supervision, plus 5 •...
  • Page 9 SIG SIL 1.2A-H S4 RELEASE CIRCUIT ISOLATE SWITCH 0.485A MAX CHARGING CURRENT JUMPERS W1 & W2 MUST BE OUT SUPERVISED, USE ONLY KIDDE-FENWAL TO ALLOW ISOLATE FUNCTION BATTERY CAT. NO. 06-115915-020 (CONSISTS OF ONLY ONE BATTERY) RESET SWITCH HOLD FOR 5 SECONDS TO CLEAR ALARM...
  • Page 10 Scorpio ™ CAUTION RELEASE CIRCUIT CONFIGURATIONS Before installing a control head on any cylinder valve, ensure the control head is in the “SET” position (e.g., actuating pin or plunger is on the fully retracted or “SET” position.) Electric control head P/N 48650001 is designed for installation on a 487 or ECS series control head only.
  • Page 11 Scorpio ™ TECHNICAL SPECIFICATIONS Operation: Style B, 10K ohm EOL. Input Power: See Table 1 for 2-wire detector compatibility • 120 Vac, 50/60 Hz 0.5 A max. • Open curcuit fault impedance: 22K ohms • 240 Vac, 50/60 Hz 0.25 A max. Auxiliary Inputs: An impedance of 25K ohms from any field wiring terminal •...
  • Page 12 Scorpio ™ THIS PAGE INTENTIONALLY LEFT BLANK. December 2001 06-235793-001 firealarmresources.com...
  • Page 13 TECHNICAL MANUAL USER FEEDBACK FORM (Use this report to indicate deficiencies, user remarks and recommendations relating to the publication. Fold on dotted line, tape and mail to KIDDE-FENWAL, Inc., 400 Main Street, Ashland, MA 01721, Attn. Documentation Manager or FAX to 508-881-8920) DATE: 1.
  • Page 14 FOLD Place Stamp Here KIDDE-FENWAL, Inc. 400 Main Street Ashland, MA 01721 Attn. Documentation Manager FOLD firealarmresources.com...
  • Page 15 firealarmresources.com...
  • Page 16: Limited Warranty Statement

    LIMITED WARRANTY STATEMENT Kidde-Fenwal, Inc. represents that this product is free from defects in material and workmanship, and it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of twenty-four (24) months from the date shipment by Kidde-Fenwal Inc.