TECHNICAL SPECIFICATIONS
Input Power:
120 Vac, 50/60 Hz 0.5 A max.
240 Vac, 50/60 Hz 0.25 A max.
An impedance of 25K ohms from any field wiring terminal
to ground except AC input power and relay outputs will
cause a ground fault condition.
Panel 24 VDC Power Requirements:
Standby Current: 35mA
Alarm Current: 200mA
Auxiliary Power:
24 Vdc at 0.25A in alarm only
Output Circuit:
One Style-Y signal circuit, 10K ohm EOL.
Rated at 24 Vdc 0.5 A (max)
Open circuit fault impedance: 13.5K ohms
Short circuit fault impedance: 4.5K ohms
When programmed for two-zone operation, pulses on first
alarm, steady output on second alarm.
Relay Outputs:
Alarm 1 relay (activates on 1st zone in alarm)
Alarm 2 relay (activates on 2nd zone in alarm or
start of release)
Note: When set up is for a single zone release, S1=ON,
Alarm 1 and Alarm 2 relays will both activate on
first alarm.
Trouble relay (normally energized)
All are Form C, rated 2A @ 250 Vac/30 Vdc
Note: For ULC installations, the form C relays are rated
for 120 V AC (150 V max to ground).
Release Output, Solenoid Style
Output circuit capable of activating 2 of the following con-
trol heads P/Ns:
48650001
890181
899175
Output held ON for 90 seconds. Circuit is power limited
and supervised on terminals 28-31.
Open circuit fault impedance: 1.7K ohms
UL Compatibility Identifier Number:
Two Detection Circuits:
Output voltage: 17.3 - 26.0 Vdc
Max. number of 2 wire smoke detectors per circuit: 15
Maximum line resistance: 50 Ohms
06-235793-001
Operation: Style B, 10K ohm EOL.
See Table 1 for 2-wire detector compatibility
Auxiliary Inputs:
Isolation Switch:
Disconnects the release output. Available by cutting jump-
ers W1 and W2.
Standby Batteries:
Requires (2) 12 Vdc 1.2A-H sealed lead acid batteries for
24 hour standby operation/5 minute alarm operation at
maximum rated load. Order separately.
Battery Charger Output:
Time Delay to Discharge:
0, 10, 20, 30, 40, 50, or 60 seconds field selectable.
Dimensions (nominal): 13.25"H x 11.0"W x 2.30"D
ORDERING INFORMATION
DESCRIPTION
Scorpio Control Panel
Above panel (240 Vac input)
(1) Battery 12 Vdc 1.2 A-H
Accessory Kit (50 10K EOL resistors)
Extra Operating Instruction Sheet
Spare Scorpio Circuit Board
Extra Scorpio Key
Canadian Scorpio
Canadian Scorpio (240 Vac Input)
C30FE1
7
firealarmresources.com
Open curcuit fault impedance: 22K ohms
Supervisory Input, Style B, 10K ohm EOL.
Manual Release Input, Style B, 10K ohm EOL.
Abort Input, Style B, 10K ohm EOL.
Open circuit fault impedance for Abort, Supervisory
and Manual release: 22K ohms
Nominal Standby Load: 35 mA
Maximum Charging Current 0.48 A
Scorpio
PART NO.
84-232000-102
84-232000-104
06-115915-020
06-129520-001
06-235883-001
06-129800-002
06-118013-001
84-232000-202
84-232000-204
December 2001