Download Print this page

Kidde Scorpio CPD 7051 Series Installation, Operation & Maintenance Manual page 7

Fire control panel

Advertisement

interface switches and indicators are located on the op-
erator interface board behind the locked cover. The en-
closure is of sufficient size to house the two 1.2 V 1.2 AH
batteries required for standby power operation.
*
An optional dead-front enclosure (P/N 06-235500-001)
is available (mandatory for use in Canada). The dead
front protects the user from access to any exposed
wiring. See Figure 1 for installation.
Four (4)
Mounting Screws,
P/N 06-250354-071
Figure 1. Dead Front Enclosure
PROGRAMMING
The control panel provides an 8 position DIP switch (S2)
for setting of the programmable functions of the unit. These
functions are set by placing the switch in either the ON or
OFF position. The following paragraphs explain the func-
tions and appropriate settings.
S2-1. Switch 2-1 allows the installer to program the con-
trol unit to activate the release output on activation of one
alarm zone or both alarm zones (cross-zoned). S2-1 OFF
= 2 zone release (cross-zoned), S2-1 ON = 1 zone re-
lease.
S2-2. Switch 2-2 is not used.
S2-3. Switch 2-3 allows the installer to program a delay
for the manual release input circuit. The manual input cir-
cuit may be either delayed or not delayed. The same de-
lays apply to this circuit when activated as to the detection
circuits (to a maximum of 30 seconds). S2-3 OFF = im-
mediate output, S2-3 ON = delayed.
S2-4, S2-5 & S2-6. Switches 2-4, 2-5 & 2-6 allow the in-
staller to program the unit with the appropriate delay (0, 10,
20, 30, 40, 50 or 60 seconds), needed for the installation.
Table 3 lists the switch positions and associated delays. (The
manual release delay will delay for 30 seconds, maximum.)
Note:
Panels with software revision 06-235252-002 or ear-
lier, made prior to date code 9735, S2-6 = ON En-
ables the abort function, S2-6 = OFF Disables the
abort function.
S2-7 & S2-8. Switches 2-7 and 2-8 allows the installer to pro-
gram the desired Abort mode for the installation. There are three
modes of Abort as explained in a previous section of this docu-
ment. S2-7 OFF = Mode 1, S2-7 ON = Mode 2, S2-8 OFF = IRI
Mode, S2-8 ON = Mode 1 or Mode 2 per S2-7.
Mode 2 and IRI Mode does not comply with UL 864.
06-235793-001
i T
m
ISOLATE SWITCH
W1 & W2. W1 & W2 are wire jumpers which allow the
installer to enable the use of the isolate switch (S4). To
enable the isolate switch cut both W1 & W2. When both
jumpers are installed the isolate switch will not disable the
release output circuit from activating the attached sup-
pression system.
PROGRAMMABLE ALARM RELAY
W8 is a wire jumper which allows the installer to program
Alarm Relay 2. To program the relay to activate on sec-
ond alarm, cut W-8. Alarm Relay 2 is programmed to ac-
tivate at the start of release when the wire jumper is
installed.
BASIC OPERATING INSTRUCTIONS
Standby Condition
Alarm Condition - Panel Programmed for One Zone
Mode
Upon receipt of an alarm from an activated detector:
Upon receipt of an alarm from an activated manual sta-
tion:
Operation of SILENCE switch:
Operation of ABORT:
3
firealarmresources.com
Table 3. Switch Settings
e
D
e
a l
y
S
4
0
e s
. c
O
F
F
1
0
e s
. c
O
N
2
0
e s
. c
O
F
F
3
0
e s
. c
O
N
4
0
e s
. c
O
N
5
0
e s
. c
O
F
F
6
0
e s
. c
O
N
Green POWER ON LED lit, all other LEDs and sounder
off.
Red Zone 1 or Zone 2 ALARM LED lit.
Sounder on.
Signal circuit devices are activated and on steady.
Programmed release time delay activated.
Red Manual Station ALARM LED lit.
Sounder on.
Signal circuit devices are activated and on steady.
Programmed release time delay activated.
Yellow SILENCE LED lit.
Sounder off.
Signal circuit devices off.
Yellow ABORT ACTIVATE LED lit.
Discharge is aborted ONLY when alarm is from a de-
tector, and abort is activated during programmed re-
Scorpio
S
5
S
6
O
F
F
O
F
F
O
F
F
O
F
F
O
N
O
F
F
O
N
O
F
F
O
F
F
O
N
O
N
O
N
O
N
O
N
December 2001

Advertisement

loading

Related Products for Kidde Scorpio CPD 7051 Series