Toshiba Q9 Plus Bypass ASD Installation & Operation Manual page 320

Hide thumbs Also See for Q9 Plus Bypass ASD:
Table of Contents

Advertisement

Connection example when using the computer link function
<Independent communication>
6
Perform computer-inverter connection as follows to send operation frequency commands from the host
computer to inverter No. 3:
Host computer
INV
INV
Given
Given
No.00
No.01
away
away
INV= inverter
"Given away": Only the inverter with the selected inverter number conducts data processing. All other
inverters, even if they have received the data, give it away and stand by to receive the
next data.
: Use the terminal block to branch the cable.
(1)
Data is sent from the host computer.
(2)
Data from the computer is received at each inverter and the inverter numbers are checked.
(3)
The command is decoded and processed only by the inverter with the selected inverter number.
(4)
The selected inverter responds by sending the processing results, together with its own inverter
number, to the host computer.
(5)
As a result, only the selected inverter starts operating in accordance with the operation frequency
command by communicating independently.
INV
INV
Given
No.02
No.03
away
F-140
: Wiring
(Host → INV)
: Data
: Response data (INV → Host)
INV
Given
No.29
No.30
away
E6581611
INV
Given
away

Advertisement

Table of Contents
loading