6. THERM-CONNECT basic

06.01 General description

The high efficiency run around coil system consists of two heat exchangers with a high counterflow ratio and a
series connection of the individual heat transfer stages.
The heat is transferred via an intermediate medium consisting of a water-glycol mixture between the exhaust air coil
and the outdoor air coils.
The brine mass flow is controlled by the three-way control ball valve depending on the power demand of the BMS.
In addition, frost protection can be controlled via this using a temperature sensor provided by the customer. This
allows the brine mass flow to be routed past the supply air coil in order to prevent ice formation on the coil. The
pump is controlled digitally by switching the operating voltage through an on-site contactor.
Exhaust air
DN
VL
Transfer points
A4
A3
Z1
" IG
Z2
" IG
A3
" IG
A4
" IG
1
" Connection
2
for
on-site frost
protection
Liter limit
WOLF Geisenfeld
Rotary valve
Fabr. Belimo
AB
type:
M
B
A
Z2
Z1
RL
VL
DN
Outside air

06.02 Control functions

• External release Pump On
• Pump starts up to set frequency.
• External power signal ( 0-10V DC) directly controls the three-way valve for power control.
• External enable pump off
• The system stops
Frost protection control:
An on-site temperature sensor for frost protection control can be integrated via the existing ½" connection in the
exhaust air flow.
Exhaust air
High pressure pump
Fabr. EBARA
DN
Supply Air
Zust.
Diese Zeichnung darf ohne unsere ausdrückliche Genehmigung weder vervielfältigt, noch dritten Personen oder Konkurrenzfirmen im Original oder
als Kopie ausgehändigt werden. Eigentums- und Urheberrecht vorbehalten.
11
Drainage and venting on site
WOLF Anlagen-Technik
Qualitätsmanagement
GmbH & Co.KG
Münchener Str. 54
zertifiziert nach
85290 Geisenfeld
DIN EN ISO 9001
Tel. 08452 / 99-0
Fax.08452 / 99-250
2018
Datum
Name
19.01.2019
F.Franz
Bearb.
Gepr.
Norm
Änderung
Datum
Name
Safety valve
6 bar
P
Expansion tank
Liters
MAßSTAB
Maßstab
Kom. THERM-CONNECT basic
Prinzipschema
Hochleistungs-KVS
Blatt
AB-
Änderungen vorbehalten
Bl

Advertisement

Table of Contents
loading

Table of Contents