INSTALLATION

Basic Installation Design and
Application Planning
Successful unit installations require proper planning
and site inspection before installation begins. Before
installing the wall mount unit, make sure that all
service and airflow clearances are met and that the
unit can meet all applicable code and regulation
requirements. Provide an inspection of both the inside
and outside of the structure by reviewing floorplans
and/or visiting the installation site.

Wall Construction

The wall must be inspected to ensure that the weight
of the unit can be supported. Be sure to review all
applicable construction codes and regulations including
seismic requirements. When inspecting wood frame
walls, the wall construction must be strong and
rigid enough to carry the weight of the unit without
transmitting any unit vibration. It is important that
the side unit wall mounting lags and optional bottom
bracket are supported by structural members inside
the wall cavity. Concrete block and brick walls must be
thoroughly inspected to ensure that they are capable of
carrying the weight of the installed unit. Metal buildings
must contain structural components to support the unit
weight. If heavily corrugated siding is present, it may
need to be trimmed and flashed similar to a window
to provide a flat, even surface to attach and seal the
unit to the wall. Heavy gauge corrugations that would
be present on shipping containers and blast-proof
structures may require the installation of a metal plate
over the corrugated area. It is important that the unit
area is weatherized and sealed to avoid air and water
infiltration into the area between the unit and the wall.

Outdoor Area Inspection

Inspect the outdoor area of the jobsite or review
construction plans and locate the area where the wall
mount is to be installed. The outdoor area must be
free from obstructions including fences, bushes and
walls that will hinder unit operation regarding outdoor
condenser airflow and unit serviceability. Do not
install units in enclosed areas that limit the amount
of ambient temperature airflow. Warm air will exit
the front condenser section of the unit, and outdoor
ambient temperature air must be able to enter side
intake condenser openings of the unit. Portable or
modular building placement must be in a way that the
wall mount units have a constant supply of outdoor air
for proper unit operation. Make sure that the service
panels of the unit are accessible. Inspect wall surfaces
for obstructions that could hinder unit installation
and servicing including outdoor electrical conduits,
junction boxes, wall drains, vent hoods, windows, doors,
overhangs and posts.
Manual 2100-720E
Page
8 of 42

Condensate Water Drainage

Review all codes and requirements for unit condensate
drainage. A plastic drain hose extends from the drain
pan in the upper section of the unit and extends
down to the unit base. An opening is supplied towards
the back of the unit base for the drain hose to pass
through, and the hose extends 1" to 2" below the unit
base. Water removed from the indoor air (condensate)
will be expelled from the unit in large amounts during
cooling operation through the hose. Units running
in cooling operation in cold outdoor below freezing
conditions can cause the condensate to freeze after
leaving the drain hose. In the event the drain hose
is connected to a drain system of some type, it must
be an open or vented type system to ensure proper
drainage throughout seasonal use.
Indoor Ducted and Non-Ducted
Applications
Air distribution inside the structure being conditioned
plays an important role in making sure the area is
a consistent temperature. Improper air distribution
can result in areas being cooler or warmer, electrical
equipment not receiving sufficient airflow or occupancy
discomfort felt inside an area. Thermostat or indoor
temperature sensor placement inside the area being
conditioned also plays an important role in indoor
climate control.

Indoor Supply Airflow

Indoor installation areas must provide a non-restrictive
path for the conditioned supply air to leave supply grilles
and registers. Inspect the area to ensure that all indoor
portions of the room or rooms will have access to supply
air. Ductwork may be used to ensure proper air circulation
and all provided ductwork guidelines and clearances must
be followed. Non-ducted applications must use a supply
louver grille installed over the supply opening inside the
room. Be sure to adjust supply deflectors to properly
disperse the conditioned supply air to all parts of the
room. Avoid closing sections of the supply grilles which
would cause unneeded supply duct pressurization.

Indoor Return Airflow

A non-restrictive path for room air returning to the
center section of the unit must be provided inside
the room. Avoid placing objects including furniture,
electronics equipment, equipment racks and cabinets
directly in front of the unit return grilles and registers.
Bard recommends at least 2' between solid objects
and return grilles or registers. Ductwork may be used to
ensure proper air circulation and all provided ductwork
guidelines and clearances must be followed. Non-
ducted applications must use a return louver grille
installed over the return opening inside the room.