Refrigerant Filter - Carrier 17/19EX Start-Up, Operation And Maintenance Instructions Manual

50/60 hz centrifugal liquid chillers with hfc-134a
Table of Contents

Advertisement

To Change the Oil
1. Open the control and oil heater circuit breaker.
2. Drain the oil reservoir by opening the oil charging valve,
26). Slowly open the valve against refrigerant pressure.
3. Change the oil filter at this time. See
4. Change the refrigerant filter at this time, see the next section,
5. Charge the machine with oil. The EX uses approximately 15 gallons (57 L), for EX and FA
(size 421-469) style compressors; 20 gallons (76 L) for FA (size 531-599) style
compressors in order to bring the level to the middle of the upper sight glass
17 and
Figure
3, Item 19). Turn on the power to the oil heater and let the PIC warm it up to
at least 140 F (60 C). Operate the oil pump manually, through the Control Test, for 2
minutes. The oil level should be between the lower sight glass and one-half full in the upper
sight glass for shutdown conditions.

Refrigerant Filter

On hermetic machines with EX compressor, a replaceable core refrigerant filter/drier is
located on the refrigerant cooling line to the motor
the refrigerant filter is located behind the compressor. The filter core should be changed once a
year, or more often if filter condition indicates a need for more frequent replacement. Change
the filter with the machine pressure at 0 psig (0 kPa) by transferring the refrigerant to the utility
(Figure
Changing Oil Filter
section.
(Figure
3, Item 29). On FA style machines,
2, Item 18 or
Figure
Refrigerant
Filter.
(Figure
3, Item
2, Item

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

17ex19ex

Table of Contents