XPM Expanion Modules technical
specifications
Table 12: Technical specifications
Power Requirement
Power Consumption
Power Source
Ambient Conditions
Communications Protocol
Device Addressing for BACnet MS/TP
Communications Bus
Processor
Memory
Input and Output Capabilities
Universal Input (UI) Resolution/ Analog
Output (AO) Accuracy
Terminations
Mounting
Housing
Dimensions (Height x Width x Depth)
Weight
20
F4-XPM Expansion Modules Installation Guide
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
14 VA maximum
Note: The VA rating does not include any power supplied to the peripheral devices
connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can
consume up to 12 VA for each BO or CO; for a possible total consumption of an
additional 84 VA (maximum).
+15 VDC power source terminals provide 100 mA total current. Only present on XPM09090
and XPM04060 models.
F4-XPM09090-0: Quantity 2-located in Universal IN terminals for active (3-wire)
input devices.
F4-XPM04060-0: Quantity 1-located in Universal Input terminals for active (3-wire)
input devices.
Operating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing
Storage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
BACnet MS/TP; Wireless also supported (at FC Bus and for Sensors) with additional
hardware.
Decimal address set via three rotary switches; valid controller device addresses 4-127
BACnet MS/TP (default);
3-wire FC Bus between the supervisory controller and expansion modules
4-wire SA Bus between equipment controller, network sensors and other sensor/actuator
devices, includes a lead to source 15 VDC supply power (from equipment controller) to
bus devices.
RX64M Renesas
32-Bit microcontroller
®
16 MB flash memory and 8 MB SDRAM
Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohms, or Binary Dry Contact
Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
Configurable Outputs Defined as 0-10 VDC or 24 VAC @500mA Triac BO
Analog Outputs: Defined as 0–10 VDC or 4–20 mA
Binary Outputs: Defined as 24 @500mA VAC Triac (external power source only)
Input: 24-bit Analog to Digital converter
Output: +/- 200 mV accuracy in 0–10 VDC applications
Input/Output: Pluggable Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 2-Wire Pluggable Screw Terminal Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jack
Horizontal on single 35 mm DIN rail mount (recommended), or screw mount on flat
surface with three integral mounting clips on controller
Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing
Protection Class: IP20 (IEC529)
XPM09090-0: 150 mm x 190 mm x 44.5 mm (5-7/8 in. x 7-1/2 in. x 2-1/8 in.) including
terminals and mounting clips
XPM04060-0 and XPM18000-0: 150 mm x 125 mm x 44.5 mm (5-7/8 in. x 4-7/8 in. x 2-1/8
in.) including terminals and mounting clips
Note: Mounting space requires an additional 50 mm (2 in.) space on top,
bottom, and front face of controller for easy cover removal, ventilation, and wire
terminations.
XPM04060-0 and XPM18000-0 0.29 kg (0.64 lb)
XPM09090-0 0.5 kg (1.1 lb)