Modbus Data Listing - Hitachi CP-X200 Instruction Manual

X200 series
Hide thumbs Also See for CP-X200:
Table of Contents

Advertisement

ModBus Data Listing

ModBus Coil List
The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
Coil Number - The network
single bit (binary) value.
Name - The functional name of the coil
R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data
Description - The meaning of each of the states of the coils
Coil
Number
0000h
(Reserved)
0001h
Run command
0002h
FW/RV command
0003h
External trip (EXT)
0004h
Trip reset (RS)
0005h
(Reserved)
0006h
(Reserved)
0007h
Intelligent input terminal 1
0008h
Intelligent input terminal 2
0009h
Intelligent input terminal 3
000Ah
Intelligent input terminal 4
000Bh
Intelligent input terminal 5
000Dh
(Not used)
000Eh
Run/Stop status
000Fh
FW/RV status
0010h
Inverter ready
0011h
(Reserved)
0012h
(Reserved)
0013h
(Reserved)
register address offset
List of Coil Numbers
Name
R/W
R
R/W 0...Stop
R/W 0...RV
R/W 0...No trip event
R/W 0...No reset condition
R
R
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
for the coil. The coil data is a
Description
1...Run (enable when A003=03)
1...FW (enable when A003=03)
1...Trip occurred
1...Reset
0...OFF *1
1...ON
0...Stop (corresponds to D003 monitor)
1...Run
0...FW
1...RV
0...Not ready
1...Ready
B − 19
B 19

Advertisement

Table of Contents
loading

Table of Contents