The cabinet can be surface or flush-mounted. If you will be flush-mounting the cabinet, the hole for the
enclosure should be 14.5" W x 24.75" H x 3-7/16" D (36.8cm W x 62.9cm H x 8.73cm D). Do not flush-
mount in a wall designated as a fire break. The Outside dimensions of the cabinet are 16.1" W x 26 ½"
H x 4-1/8" D (40.64cm W x 66.68cm H x 10.48cm D).
Follow these steps to properly mount the cabinet.
1. On the mounting surface install two screws level with each other 11" apart.
Figure 4-57 Cabinet Flush Mount Dimensions and Mounting Hole Locations
2. Install the cabinet onto the two mounting screws and tighten the screws.
3. Insert two screws into the two bottom mounting holes.
4.8.3

Mounting the ECS-DUAL50WBD Board Only

Note: Installation and wiring of this device must be done in accordance with NFPA 72 and local
ordinances.
1. Make certain that AC and DC power have been removed from the panel.
2. If this module is a replacement for an existing ECS-DUAL50W, remove the screws which secure
the board to the enclosure.
3. Secure the supplied bracket to the top mounting bracket on the ECS-DUAL50W with the two
Key Holes
4-44
Board mounting
bracket
Bottom Mounting Holes
151455