Agency Listings, Approvals, and Requirements
2.2.4
Requirements for Remote Station Protected Fire Alarm
Systems
Minimum system requirements are one Honeywell Silent Knight addressable initiating device and
either a 5220, Keltron 3158 or the built-in Digital Alarm Communicator Transmitter (DACT).
1.
Do not exceed the current load restrictions shown in Section 3.7.5.
2. The AC Loss Hours option must be set from 1-3 hours.
2.2.5
Requirements for the Installation of Carbon Monoxide (CO)
Detection and Warning Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
2-3