Factory Set Points -
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to "2".
Then go to A1-03 and change it to "1110" and press
enter. The drive is now reset back to the settings
programmed at Greenheck. This option is not
available on the J1000.
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
A1-01
Access Level
b1-17
VFD Start-Up Setting
C1-01
Acceleration Time
C1-02
Deceleration Time
C6-02
Carrier Frequency
d2-02
Ref Lower Limit
E2-01
Motor Rated FLA
H3-04
Terminal A1 Bias
A1-01
Access Level
MULTISPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
A1-01
Access Level
b1-01
Reference Source (Frequency)
b1-17
VFD Start-Up Setting
C1-01
Acceleration Time
C1-02
Deceleration Time
C6-02
Carrier Frequency
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
d1-04
Frequency Reference 4
d2-02
Ref Lower Limit
E2-01
Motor Rated FLA
Multfunction Input Sel 4
H1-04
(Terminal S4)
Multifunction Input Sel 5
H1-05
(Terminal S5)
Multifunction Input Sel 6
H1-06
(Terminal S6)
H3-10
A2 Not Used
A1-01
Access Level
continued
Setting
V1000
J1000
2
2
1
1
30 sec.
30 sec.
30 sec.
30 sec.
1
1
50%
50%
Motor
Motor
FLA
FLA
50%
50%
0
0
Setting
V1000
J1000
2
2
0
0
1
1
30 sec.
30 sec.
30 sec.
30 sec.
1
1
60 Hz
60 Hz
40 Hz
40 Hz
30 Hz
30 Hz
60 Hz
60 Hz
50%
50%
Motor
Motor
FLA
FLA
3
3
4
4
5
NA
F
NA
0
0
CO 2 SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C0 2 DROPS bELOW 700 PPM)
(FULL SPEED WHEN C0 2 RISES AbOVE 800 PPM)
Parameter
A1-01
Access Level
b1-01
Reference Source (Frequency)
b1-17
VFD Start-Up Setting
C1-01
Acceleration Time
C1-02
Deceleration Time
C6-02
Carrier Frequency
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d2-02
Ref Lower Limit
E2-01
Motor Rated FLA
H3-10
A2 Not Used
A1-01
Access Level
Model PVe Heat Recovery Unit
Setting
V1000
J1000
2
2
0
0
1
1
30 sec.
30 sec.
30 sec.
30 sec.
1
1
60 Hz
30 Hz
30 Hz
60 Hz
50%
50%
Motor
Motor
FLA
FLA
F
NA
0
0
13