Download Print this page

Greenheck FSD-312 Specifications page 5

Combination fire smoke dampers steel airfoil blades ul 555s leakage class ii ul555 1 1/2 hour fire resistance rating

Advertisement

AmCA 5.5 Pressure drop
* Sizes are in inches.
12 in. x 12 in. (305mm x 305mm)
Velocity
Pressure Drop
(fpm)
(in. wg)
500
0.04
1000
0.18
1500
0.42
2000
0.75
2500
1.17
3000
1.68
3500
2.29
4000
2.09
24x24
24 in. x 24 in. (610mm x 610mm)
Velocity
Pressure Drop
(fpm)
(in. wg)
500
0.03
1000
0.13
1500
0.29
2000
0.52
2500
0.81
3000
1.17
3500
1.60
4000
2.14
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
R
grams. The AMCA Certified Ratings Seal applies
to air performance ratings only.
D
36x36
12x48
36in. x 36 in. (914mm x 914mm)
Velocity
Pressure Drop
(fpm)
(in. wg)
500
0.03
1000
0.12
1500
0.27
2000
0.48
2500
0.75
3000
1.08
3500
1.48
4000
1.93
4 (W) (H)
3.14
*
12in. X 48 in. (305mm x 1219mm)
Velocity
Pressure Drop
(fpm)
(in. wg)
500
0.03
1000
0.12
1500
0.27
2000
0.49
2500
0.77
3000
1.11
3500
1.51
4000
1.97
Fsd-312
48 in. x 12 in. (1219mm x 305mm)
Velocity
Pressure Drop
(fpm)
(in. wg)
500
0.03
1000
0.14
1500
0.32
2000
0.57
2500
0.89
3000
1.28
3500
1.75
4000
2.29

Advertisement

loading