Greenheck FSD-312 Specifications
Greenheck FSD-312 Specifications

Greenheck FSD-312 Specifications

Combination fire smoke dampers steel airfoil blades ul 555s leakage class ii ul555 1 1/2 hour fire resistance rating

Advertisement

Quick Links

APPLICATION
Model FSD-312 is a high performance combination fire smoke
damper with class II leakage. High strength airfoil blades ensure the
lowest resistance to airflow in HVAC systems with velocities to 3000
fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may
be installed vertically (with blades running horizontal) or horizontally
and is rated for airflow and leakage in either direction.
RATINgs
UL 555 Fire Resistance Rating:
Fire Rating:
Dynamic Closure Rating: Actual ratings are size dependent
Max. Velocity:
Max. Pressure:
UL555S Leakage Rating:
Leakage Class:
Operational Rating:
Max. Velocity:
Max. Pressure:
Maximum Temperature: 350°F (177°C)- depending upon the
sTANdARd CONsTRuCTION
Frame:
Blades:
seals:
Linkage:
Closure device:
Axles:
Bearings:
sIze LImITATIONs:
minimum size:
maximum size:
Single Section:
Multiple Section:
Vertical Only:
OPTIONAL FeATuRes:
• RRL/OCI (Open closed indication switches)
• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's
available
• TOR (remote override closure allows damper to perform smoke
management functions during a fire emergency.)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• POC retaining angles
• Smoke detectors
• Momentary Switch
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
• Security Bars
• Sealed transitions and sleeves
Combination Fire smoke dampers
1½ hours
up to 3000 fpm (15.2 m/s)
4 in. wg (1 kPa)
II
Actual ratings are size dependent
up to 3000 fpm (15.2m/s)
4 in. wg (1 kPa)
actuator
5 in. x 1 in. (127mm x 25 mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes less
than 17 in. (432mm)
Double skin airfoil shape of
galvanized steel with full length
structural reinforcement. 14 ga.
(2 mm) equivalent thickness.
Extruded silicone rubber blade seals.
Flexible stainless steel jamb seals.
Concealed in jamb.
RRL 165°F (74°C)
1 ⁄2 in. (13mm) dia. plated steel.
Bronze sleeve type.
8 in. W x 6 in. H
(203 mm W x 152mm H)
32 in. W x 50 in. H
(813mm W x 1270mm H)
96 in. W x 50 in. H
(2435mm W x 1270mm H)
128 in. W x 100 in. H
(3251mm W x 2540mm H)
UL555 1
Model FSD-312 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO uniform Building Codes
CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
"uL CLAssIFIed (see complete marking on prod-
uct)"
"uL CLAssIFIed to Canadian safety standards
(see complete marking on product)"
Standard 555 & 555S (Listing #R13317)
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air
R
performance ratings only.
LH
W*
*W&H dimensions furnished approximately 1 /4 in. ( 6 mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation instructions available at www.greenheck.com
model Fsd-312
Steel Airfoil Blades
UL 555S Leakage Class II
Hour Fire Resistance Rating
1
2
RH
H*

Advertisement

loading

Summary of Contents for Greenheck FSD-312

  • Page 1 II leakage. High strength airfoil blades ensure the lowest resistance to airflow in HVAC systems with velocities to 3000 fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may be installed vertically (with blades running horizontal) or horizontally and is rated for airflow and leakage in either direction.
  • Page 2: Pressure Drop Data

    Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system. Figure 5.3 Figure 5.2 Figure 5.5 Fsd-312 (1.201 kg/m 4 (W) (H) 3.14 4 (W) (H) 4 (W) (H) 3.14...
  • Page 3 0.87 4000 0.88 Greenheck Fan Corporation certifies that the model FSD-312 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs.
  • Page 4 0.42 4000 0.38 Greenheck Fan Corporation certifies that the model FSD-312 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams.
  • Page 5 2.14 4000 1.93 Greenheck Fan Corporation certifies that the model FSD-312 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams.
  • Page 6: Application Data

    The drawings below and corresponding table show the position of the FSD-312 damper when mounted in a factory sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installa- tion of retaining angles and duct connections.
  • Page 7 Transitioned damper When a fire/smoke damper is being used in conjunction with round or oval ductwork, the FSD-312 can be supplied in a factory sleeve with round or oval transitions on both ends of dimensions the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show over- all damper size.