7½- to 12½-ton self-contained packaged heat pump

Advertisement

H
k
e
d
eat
it
leCtriCal
ata
Model and
Heat Kit Usage
CPH102***3B***
EHK3-16
EHK3-30
EHK3-45
Model and
Heat Kit Usage
CPH102***4B***
EHK4-16
EHK4-30
EHK4-45
Model and
Heat Kit Usage
CPH102***7B***
EHK7-16
EHK7-30
EHK7-45
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
^ - EHK Heater Kits above require a three-phase power supply
W C
f
k
orreCtion
aCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
Correction Factor
1
kW Correction Factor for 480V Units
Supply Voltage
460
Correction Factor
0.92
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
Correction Factor
0.95
Multiply rated kW by correction factor to get actual kW.
SS-CPH90-150
— 8½ t
onS
MCA¹
MOP² (amps)
at 240V
at 240V
43
50
88
90
133
150
173
175
MCA¹
MOP² (amps)
at 480V
at 480V
20
25
42
45
65
70
84
90
MCA¹
MOP² (amps)
at 575V
at 575V
17
20
36
40
55
60
71
80
230
220
0.93
0.82
440
430
0.84
0.8
550
540
0.91
0.88
www.goodmanmfg.com
Recommended
Actual kW
Airflow Range
at 240V
(Downshot)
15
3400 - 3825 CFM
35
3400 - 3825 CFM
43
3400 - 3825 CFM
Recommended
Actual kW
Airflow Range
at 480V
(Downshot)
15
3400 - 3825 CFM
30
3400 - 3825 CFM
43
3400 - 3825 CFM
Recommended
Actual kW
Airflow Range
at 575V
(Downshot)
15
3400 - 3825 CFM
30
3400 - 3825 CFM
43
3400 - 3825 CFM
210
208
0.78
0.76
m
a
inimum
irfloW for
Heater Size (kW)
15
30
43
P
S
roduCt
PeCifiCationS
Recommended
Airflow Range
(Horizontal)
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
Recommended
Airflow Range
(Horizontal)
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
Recommended
Airflow Range
(Horizontal)
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
e
H
leCtriC
eat
Min. CFM
Min. CFM
Down-shot
Horizontal
3,400
3,400
3,400
3,400
3,400
3,400
21