7½- to 12½-ton self-contained packaged heat pump

Advertisement

P
S
roduCt
PeCifiCationS
H
k
e
d
— 7½ t
eat
it
leCtriCal
ata
Model and
Heat Kit Usage
CPH090***3B***
EHK3-16
EHK3-30
EHK3-45
Model and
Heat Kit Usage
CPH090***4B***
EHK4-16
EHK4-30
EHK4-45
Model and
Heat Kit Usage
CPH090***7B***
EHK4-16
EHK4-30
EHK4-45
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
w C
f
k
orreCtion
aCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
Correction Factor
1
kW Correction Factor for 480V Units
Supply Voltage
460
Correction Factor
0.92
For other voltage, use voltage² / 480²
kW Correction Factor for 575V Units
Supply Voltage
560
Correction Factor
0.95
Multiply rated kW by correction factor to get actual kW.
20
onS
MCA¹
MOP² (amps)
at 208 / 240V
at 208 / 240V
40
50
74 / 85
80 / 90
113 / 130
120 / 150
147 / 169
150 / 175
MCA¹
MOP² (amps)
at 208 / 240V
at 208 / 240V
19
25
42
45
64
70
84
90
MCA¹
MOP² (amps)
at 208 / 240V
at 208 / 240V
14
15
32
35
51
60
68
70
230
220
0.93
0.82
440
430
0.84
0.8
550
540
0.91
0.88
www.goodmanmfg.com
Actual kW
at 240V
15
30
43
Actual kW
at 240V
15
30
43
Actual kW
at 240V
15
30
43
210
208
0.78
0.76
m
Recommended
Airflow Range
3000-3375 CFM
3000-3375 CFM
3000-3375 CFM
Recommended
Airflow Range
3000-3375 CFM
3000-3375 CFM
3000-3375 CFM
Recommended
Airflow Range
---
---
---
a
e
H
inimum
irflow for
leCtriC
eat
Heater Size (kW)
Minimum CFM
15
3,000
30
3,000
43
3,000