Goodman CPC CONVERCIAL SS-CPC90-150 User Manual page 13

7½- to 12½-ton three-phase packaged air conditioners

Advertisement

h
k
E
d
Eat
it
lECtRiCal
ata
Model and
Heat Kit Usage
CPC120***3B***
EHK3-16
EHK3-30
EHK3-45
Model and
Heat Kit Usage
CPC120***3H***
EHK3-16
EHK3-30
EHK3-45
Model and
Heat Kit Usage
CPC120***4B***
EHK4-16
EHK4-30
EHK4-45
Model and
Heat Kit Usage
CPC0120***7B***
EHK7-16
EHK7-30
EHK7-45
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
kw C
f
oRRECtion
aCtoRs
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
Correction Factor
kW Correction Factor (for 480V Units)
Supply Voltage
460
Correction Factor
0.92
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
Correction Factor
0.95
Multiply rated kW by correction factor to get actual kW.
SS-CPC90-150
(B
o
, h
m
lowER
nly
Eat
odE
MCA¹
MOP² (amps)
at 208 / 240V
at 208 / 240V
49
60
48 / 55
50 / 60
87 / 100
90 / 100
121 / 139
125 / 150
MCA¹
MOP² (amps)
at 208 / 240V
at 208 / 240V
50
60
49 / 57
50 / 60
88 / 102
90 / 110
122 / 141
125 / 150
MCA¹
MOP² (amps)
at 480V
at 480V
24
30
27
30
50
50
70
70
MCA¹
MOP² (amps)
at 575V
at 575V
17
20
22
25
41
45
57
60
230
220
210
1
0.93
0.82
0.78
440
430
0.84
0.8
550
540
0.91
0.88
www.goodmanmfg.com
) — 10 t
ons
Actual kW
Recommended
at 240V
Airflow Range
15
3500 - 4500 CFM
30
3500 - 4500 CFM
43
4000 - 4500 CFM
Actual kW
Recommended
at 240V
Airflow Range
15
3500 - 4500 CFM
30
3500 - 4500 CFM
43
4000 - 4500 CFM
Actual kW
Recommended
at 480V
Airflow Range
15
3500 - 4500 CFM
30
3500 - 4500 CFM
43
4000 - 4500 CFM
Actual kW
Recommended
at 575V
Airflow Range
15
3500 - 4500 CFM
30
3500 - 4500 CFM
43
4000 - 4500 CFM
208
0.76
m
a
inimum
iRflow foR
Heater Size (kW)
15
30
43
p
s
RoduCt
pECifiCations
E
h
lECtRiC
Eat
Min. CFM
Min. CFM
Down-shot
Horizontal
4,000
4,000
4,000
4,000
4,000
4,000
13