Certification
6.2 EMC and Environmental Type Tests
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-14
IEC 60068-2-78
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-2
IEC 60255-21-3
44
Test
IEEE 1613
IEEE 1613
IEEE 1613
IEEE 1613.1
IEC 61000-4-10
Test
Cold Temperature
Cold Storage
Dry Heat
Dry Heat Storage
Humidity (Damp
Heat, Cyclic)
Change of
Temperature
Humidity (Damp
Heat, Cyclic)
IEC 60529
Description
Oscillatory
Signal Ports
DC Power Ports
HV Impulse
Signal Ports
DC Power Ports
AC Power Ports
Dielectric
Signal Ports
Strength
DC Power Ports
AC Power Ports
Damped
Enclosure Ports
Oscillating
Magnetic
Field
Description
Test Ad
Test Ab
Test Bd
Test Bd
Test Dd
Test Nb
Test Cab
Vibration
Shock
Bump
Seismic
Ingress Protection
Test Levels
2.5 kV Common
Mode @ 1 MHz
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
2.8 kVDC or 2 kV
2 kV
100 A/m for 1 s (100
kHz and 1 MHz)
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
5 Cycles @
-40 to 85 °C
(-40 to 185 °F)
10 Days @ 55 °C
(131 °F), 6 Cycles
2 g @ 10 to 150 Hz
30 g @ 11 ms
10 g @ 16 ms
Method A
IP4x
RUGGEDCOM RSG907R
Installation Manual, 02/2021, C79000-G8976-1387-12
 
 
 
 
 
 
 
Class 2
Class 2
Class 1
Class 2
 