Carrier AQUAFORCE 30XA080-500 Installation Instructions Manual page 72

Air-cooled liquid chillers
Table of Contents

Advertisement

Table 8 — 30XA140-500 Electrical Data, Dual Point (High Ambient Option) (cont)
UNIT VOLTAGE
NUMBER
UNIT
OF
Supplied
V-Hz
30XA
COND
(3 Ph)
Min Max
FANS
230-60 207 253
6/4
200-60 187 220
6/4
140
460-60 414 506
6/4
575-60 518 633
6/4
380-60 342 418
6/4
230-60 207 253
6/4
200-60 187 220
6/4
160
460-60 414 506
6/4
575-60 518 633
6/4
380-60 342 418
6/4
230-60 207 253
6/6
200-60 187 220
6/6
180
460-60 414 506
6/6
575-60 518 633
6/6
380-60 342 418
6/6
230-60 207 253
6/6
200-60 187 220
6/6
200
460-60 414 506
6/6
575-60 518 633
6/6
380-60 342 418
6/6
230-60 207 253
7/6
200-60 187 220
7/6
220
460-60 414 506
7/6
575-60 518 633
7/6
380-60 342 418
7/6
230-60 207 253
7/6
200-60 187 220
7/6
240
460-60 414 506
7/6
575-60 518 633
7/6
380-60 342 418
7/6
460-60 414 506
9/6
260
575-60 518 633
9/6
380-60 342 418
9/6
460-60 414 506
9/7
280
575-60 518 633
9/7
380-60 342 418
9/7
460-60 414 506
10/6
300
575-60 518 633
10/6
380-60 342 418
10/6
460-60 414 506
9/9
325
575-60 518 633
9/9
380-60 342 418
9/9
460-60 414 506
9/9
350
575-60 518 633
9/9
380-60 342 418
9/9
460-60 414 506
8/12
400
575-60 518 633
8/12
380-60 342 418
8/12
460-60 414 506
8/14
450
575-60 518 633
8/14
380-60 342 418
8/14
460-60 414 506
8/14
500
575-60 518 633
8/14
380-60 342 418
8/14
LEGEND
ICF
— Instantaneous Current Flow
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
WD
— Wye-Delta
XL
— Across-the-Line
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
7.5 HP PUMP, 3450 RPM
ICF
MCA
MOCP
WD
383.8/235.1 600/350 660.8/414.4
422.6/259.0 700/400 756.7/473.4
191.9/117.5 300/175 330.4/207.2
962.4/578.2 225/150 191.9/121.1 300/175 330.4/210.8
147.7/ 90.7 225/125 263.9/165.6
769.9 /462.6 175/110 147.7/ 93.5 225/125 263.9/168.4
223.9/138.0 350/200 400.2/251.2
1165.2/700.2 300/175 223.9/142.4 350/200 400.2/255.5
434.8/272.3 700/400 828.8/414.4
478.1/299.6 800/450 950.7/473.4
216.9/135.7 350/200 414.4/207.2
1222.4/578.2 300/175 216.9/139.3 350/200 414.4/210.8
167.0/105.2 250/150 331.9/165.6
977.9/462.6 200/125 167.0/108.1 250/150 331.9/168.4
253.3/159.5 400/250 501.2/251.2
1480.2/700.2 300/200 253.3/163.8 400/250 501.2/255.5
10 HP PUMP, 3450 RPM
Rec
Fuse
MCA
MOCP
XL
Size
450/300 383.8/242.3 600/350 660.8/421.6
500/300 422.6/266.9 700/400 756.7/481.4
600/350 434.8/279.5 700/400 828.8/421.6
600/350 478.1/307.6 800/450 950.7/481.4
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps
is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps
is 250 kcmil to 500 kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
72
CONTROL CIRCUIT
ICF
Rec
Voltage
Fuse
1 PH,
WD
XL
Size
60 Hz
450/300
115
500/350
115
962.4/581.8 225/150
115
769.9/465.4 175/110
115
1165.2/704.5 300/175
115
600/350
115
600/400
115
1222.4/581.8 300/175
115
977.9/465.4 200/125
115
1480.2/704.5 300/200
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
MCA
and
MOCP
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50

Advertisement

Table of Contents
loading

Table of Contents