Carrier AQUAFORCE 30XA080-500 Installation Instructions Manual page 47

Air-cooled liquid chillers
Table of Contents

Advertisement

FD
CONTROL
BALANCING VALVE/
SHUT OFF*
VIBRATION
ELIMINATORS*
PUMP
LEGEND
FD
— Fused Disconnect
Airflow Through Condenser
Chilled Water Piping
Power Wiring
*Field-installed.
Fig. 19A — 30XA Typical Piping and Wiring (Units without Hydronic Package)
FIELD-SUPPLIED
FUSED DISCONNECT
CONTROL POWER
NOTES:
1. Chiller must be installed level to maintain proper
compressor oil return and hydraulics.
2. Wiring and piping shown are general points-of-
connection guides only and are not intended for a
specific installation. Wiring and piping shown are
for a quick overview of system and are not in
accordance with recognized standards.
3. All wiring must comply with applicable local and
national codes.
4. All piping must follow standard piping techniques.
Refer to Carrier System Design Manual or appro-
priate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers)
handbook for details.
5. Air separator required as close to chiller as possi-
ble (except primary/secondary systems).
6. 20 mesh strainer required for open loop systems.
Fig. 19B — 30XA Typical Piping and Wiring (Units with Hydronic Package)
STRAINER*
GATE VALVE*
DRAIN
PRESSURE/
SHUTOFF
TEMPERATURE TAPS*
VALVE
NOTES:
1. Chiller must be installed level to maintain proper compressor oil return.
2. Piping shown are general points-of-connection guides only and are not
intended for a specific installation. Wiring and piping shown are for a quick
overview of system and are not in accordance with recognized standards.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System
Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) handbook for details.
5. A 20 mesh strainer is required withinh 10 ft (3 m) of the cooler.
BALANCING VALVE/
SHUTOFF*
VIBRATION
ELIMINATORS*
47
AIRFLOW
PRESSURE/
TEMPERATURE
TAPS*
DRAIN SHUTOFF VALVE
STRAINER*
GATE VALVE*
PUMP
*Field-installed.
POWER
FD
a30-4114
FIELD-SUPPLIED
FUSED DISCONNECT
UNIT POWER
LEGEND
Airflow Through Condenser
Power Wiring
Chilled Water Piping