2.5.2 Connecting Low Dc Power - Siemens SIMATIC NET RUGGEDCOM RX1510 Installation Manual

Rugged multi service platforms
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RX1510:
Table of Contents

Advertisement

6.
Using a #10 ring lug and #10-32 screw, secure the ground terminal on the pow-
er source to the ground connection on the device. Make sure the lug is tight-
ened to 1.1 N·m (9.5 lbf·in).
Figure 2.7
7.
Install the safety cover over the terminal block.
2.5.2
Connecting Low DC Power
To connect a low DC power supply to the device, do the following:
CAUTION
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a 12, 24 or 48 VDC power supply terminal block.
Damage to the power supply may occur.
Note
The RUGGEDCOM RX1510 works with both positive VDC power supplies and negative
VDC power supplies.
Note
The screw terminal block is installed using Phillips screws and compression plates, al-
lowing either bare wire connections or crimped terminal lugs. Use #6 size ring lugs
for secure, reliable connections.
RUGGEDCOM RX1510
Installation Manual, 12/2019, C79000-G8976-1055-16
All manuals and user guides at all-guides.com
1
2
#10 Ring Lug
1
#10-32 Screw
2
Connection from External Power Source
3
Ground Connection
4
Ground Connection
2.5.2 Connecting Low DC Power
3
4
Installing the Device
13