Point Name/Description
Occupied Cooling 1 – Yellow
The space temperature must be greater than the Occupied Cooling 1 setpoint for
the VVT Master to consider the zone a cooling caller in a linked system. In a single-
zone application, the cooling requirement begins as soon as the space
temperature exceeds the Occupied Cooling setpoint. We recommend that the
Occupied Cooling 1 value be set no less than 0.5°F above the Occupied Cooling
setpoint.
Occupied Cooling 2 – Orange
The space temperature must be greater than the Occupied Cooling 2 setpoint to
generate a high space temperature alarm. We recommend that this value be set
no less than 0.5°F above the Occupied Cooling 1
Unoccupied Setpoints
Point Name/Description
Unoccupied Heating
– Gray
The heating setpoint the controller maintains while in unoccupied mode.
Unoccupied Cooling
– Gray
The cooling setpoint the controller maintains while in unoccupied mode.
Unoccupied Heating 1 – Light Blue
The space temperature must be less than the Unoccupied Heating 1 setpoint for the VVT
Master to consider the zone an unoccupied heating caller in a linked system. In a single-zone
application, the unoccupied heating requirement begins as soon as the space temperature falls
below the Unoccupied Heating setpoint. We recommend that the Unoccupied Heating 1 value
be set no less than 0.5°F below the Unoccupied Heating
Unoccupied Heating 2 – Dark Blue
The space temperature must be less than the Unoccupied Heating 2 setpoint to generate an
unoccupied low space temperature alarm. We recommend that this value be set no less than
0.5°F below the Unoccupied Heating 1
Unoccupied Cooling 1 – Yellow
The space temperature must be greater than the Unoccupied Cooling 1 setpoint for the VVT
Master to consider the zone an unoccupied cooling caller in a linked system. In a single-zone
application, the unoccupied cooling requirement begins as soon as the space temperature
exceeds the Unoccupied Cooling setpoint. We recommend that the Unoccupied Cooling 1 value
be set no less than 0.5°F above the Unoccupied Cooling
Unoccupied Cooling 2 – Orange
The space temperature must be greater than the Unoccupied Cooling 2 setpoint to generate an
unoccupied high space temperature alarm. We recommend that this value be set no less than
0.5°F above the Unoccupied Cooling 1
RTU Open
setpoint.
setpoint.
setpoint.
setpoint.
setpoint.
Default
Range: -40 to 245°F
Demand Level
Occupied
1
2
75°F
76°F
77°F
76°F
78°F
78°F
Default/Range
D:
55°F
R:
45 to 100°F
D:
90°F
R:
-40 to 245°F
D:
54°F
R:
-40 to 245°F
D:
52°F
R:
-40 to 245°F
D:
91°F
R:
-40 to 245°F
D:
93°F
R:
-40 to 245°F
3
79°F
81°F
63