Point Name/Description
Continuous Occupied Exhaust – Configures the exhaust fan control strategy (BO-8). If Yes,
the power exhaust runs continuously in occupied mode and is off in unoccupied mode. If
No, the power exhaust is controlled by the
Indoor CO2 Sensor Value @min (ma)
the appropriate input channel.
Indoor CO2 Sensor Value @max (ma)
the appropriate input channel.
Outdoor CO2 Sensor Value @min (ma)
at the appropriate input channel.
Outdoor CO2 Sensor Value @max (ma)
at the appropriate input channel.
RTU Open
Power Exhaust Setpoint.
– The CO2 value that corresponds to a 4mA input at
– The CO2 value that corresponds to a 20mA input at
– The CO2 value that corresponds to a 4 mA input
– The CO2 value that corresponds to a 20 mA input
Default/Range
D:
No
R:
No/Yes
D:
0ppm
R:
0 to 9999 ppm
D:
2000 ppm
R:
0 to 9999 ppm
D:
0ppm
R:
0 to 9999 ppm
D:
2000 ppm
R:
0 to 9999 ppm
41