Firing Rates - Riello RLS 310/EV O2 MX Modulating Operation

Dual fuel light oil/ gas burners
Table of Contents

Advertisement

4.8

Firing rates

The MAXIMUM OUTPUT is chosen from within the diagram area
(Fig. 3).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
Model
RLS 310
RLS 410
RLS 510
RLS 610 Gas
RLS 610 Light oil
20182250
Technical description of the burner
kW
600
640
660
1000
1300
RLS 410/M MX
Thermal power – kW
RLS 310/M MX
Thermal power – kW
The firing rate value (Fig. 3) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
WARNING
shown on page 24.
Pre-calibration of the combustion head only for
the burner model RLS 310/M MX:
If the maximum burner output of the burner falls
WARNING
within:
- area A of the firing rate, it is necessary to replace
the gas nozzles with those supplied (No. 8 gas
nozzles Ø 5,3), Fig. 17 on page 23.
- area B of the firing rate, no modifications are re-
quired.
10
GB
20096600
Fig. 3