Pump Electrical Data; Accessory Tank Electrical Data - Carrier AQUASNAP 30RAP010-060 Installation Instructions Manual

Liquid chillers with comfortlink controls
Hide thumbs Also See for AQUASNAP 30RAP010-060:
Table of Contents

Advertisement

PUMP OPTION
1, 8
2, 9
3, B
4, C
5, 6, D, F
7, G
LEGEND
FLA — Full Load Amps
NOTES:
1. Units are suitable for use on electrical systems where voltage sup-
plied to the unit terminals is not below or above the listed minimum
and maximum limits. Maximum allowable phase imbalance is: volt-
age, 2%; amps 10%.
UNIT VOLTAGE
(V-Hz)
208/230-60
460-60
575-60
380-60
LEGEND
FLA
— Full Load Amps
Table 15 — Pump Electrical Data
PUMP SIZE
PUMP RPM
3500
3500
1.0 HP
3500
3500
3500
3500
1.5 HP
3500
3500
3500
3500
2.0 HP
3500
3500
3500
3500
3.0 HP
3500
3500
3500
3500
5.0 HP
3500
3500
3500
3500
7.5 HP
3500
3500
Table 16 — Accessory Tank Electrical Data
UNIT VOLTAGE
V-Hz (3 Ph)
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
208/230-60
380-60
460-60
575-60
2. All units/modules have single point primary power connection.
(Each unit/module requires its own power supply.) Main power must
be supplied from a field-supplied disconnect.
3. The unit control circuit power transformer (24 v, single-phase for all
voltages) is factory supplied.
4. Cooler heaters are wired into the main power circuit so they are
always operable as long as the disconnect is on, even if any safety
device is open, and the unit ON/OFF switch is in the OFF position.
ACCESSORY PART NO.
30RA-900---
050
051
052
050
051
052
050
051
052
050
051
052
27
FLA
(each)
3.3
2.0
1.6
1.3
4.4
2.7
2.2
1.8
5.6
3.3
2.7
2.1
8.6
4.7
3.9
3.1
13.4
7.5
6.2
5.0
20.0
11.3
9.4
7.5
FLA
11.3
11.3
22.6
5.7
5.7
11.3
4.5
4.5
9.1
6.8
6.8
13.7