Operation; To Start Unit; To Shut Down Unit; Sequence Of Operation - Carrier 90MA/MF/MU Installation, Operation And Service Manual

Marine/industrial single package cooling unit design series two
Table of Contents

Advertisement

On extended voltage (208/230- -v)
CONTROL WIRING - -
units, the control transformer is factory wired for 208- -v
usage. If unit is to be used on 230- -v system, reconnect
primary wiring on transformer. See Figure 13 (004/006
size) or Figure 15 (008/012 size).
On all units, the thermostat is factory installed. A
sensing element is provided in the return air. To wire
these units to a remote thermostat, or to a remote control
switch and thermostat, refer to unit Wiring Diagram or
contact your Carrier Transicold representative.
4.

OPERATION

CAUTION
Compressor crankcase heater must be ener-
gized for 24 hours prior to start up to prevent
compressor bearing damage.
4.1

To Start Unit

a. Thoroughly inspect exterior of unit. Clean and dust
up debris, then wash with mild soap and water solu-
tion.
b. On 008 & 012 size units, ensure compressor dis-
charge, suction and liquid service valves are open.
The valves are accessible from the front of the unit.
To open valve, turn counterclockwise. After opening,
replace and tighten valve cap to prevent leakage.
Check oil level in compressor sight glass. If level is
below glass, add oil to bring level to approximately
1/4 glass. If level is above bottom of glass, do not re-
move any oil until the crankcase heater has been ener-
gized for at least twenty- -four hours.
c. With selector switch in OFF position, turn main pow-
er on. Leave power on for 24 hours so that crankcase
heater can drive off accumulated refrigerant.
d. If desired, the selector switch may be placed in the
FAN position during the crankcase warm- -up period.
On first start- -up, check fan speed (Table 1 through
Table 2) and rotation (Figure 1). If fan requires ad-
justment, refer to paragraph 5.3.
62--10458--00
e. Allow crankcase heater to remain energized (unit
power on) for at least 24 hours. Open any valves in
condenser cooling water supply lines and then set se-
lector switch at COOL position. If room temperature
is above thermostat setting compressor will start. On
first start- -up, set water regulating valve. (Refer to
paragraph5.7.)
f. Set thermostat for comfort as desired.
4.2

To Shut Down Unit

a. Turn selector switch to OFF position. Do not shut off
main power except to service unit. The crankcase
heater is operative only when main power is on. (Re-
fer to paragraph 5.12).
b. If unit is to be used for winter heating, set selector
switch at HEAT position and re- -set thermostat at de-
sired setting.
c. If unit may be exposed to freezing temperatures, drain
water from condenser and water piping. Add a non-
corrosive antifreeze to residual water in system.
4.3

Sequence Of Operation

Unit operation is dependent on the position of the mode
selector switch. (See note 3, Figure 14
Operation sequence for each switch position is provided
in the following paragraphs.
OFF POSITION: With correct voltage supplied at the
field power supply terminals, see
power flows through normally closed crankcase heater
relay (CHR) contacts (CHR, 4/5) to energize the
crankcase heater (CH).
TO PLACE THE UNIT IN THE FAN MODE: The
switch (SW) is placed in the FAN position to supply 24
volt control power, to energize indoor fan contactor
(IFC). Energizing IFC closes contacts (IFC, 11/21,
12/22 & 13/23) to energize the motor. Operation of the
crankcase heater is maintained.
TO PLACE THE UNIT IN THE COOL MODE: The
switch (SW) is placed in the COOL position. With
thermostat (T- -LOW) calling for cooling (closed to
contacts R & W) control power flows from TRAN
through T- -LOW, SW and compressor lockout (CL)
normally closed contacts to the discharge pressure
switch (DPS). On 008/012 size units, flow continues
through the compressor internal protector (IPC),
compressor overloads (OLA & OLB) and the suction
pressure switch (SPS), to energize CHR. On 004/006
size units, flow continues directly thorough the suction
pressure switch to energize CHR.
Energizing CHR opens contacts CHR 4- -5 to
de- -energize CH and closes contacts CHR 1- -3 and
energize the compressor contactor (CC). Energizing CC
closes its contacts to start the compressor motor (C).
Operation of the indoor fan motor (IFM) is maintained.
On 90MU units, power also flows from terminal TB1- -5
to energize condenser fan relay (CFR). Energizing CFR
closes its contacts to supply power to the field supplied
condenser fan relay.
012 size units are fitted with a two stage cooling system.
On these units, if thermostat switch T- -HIGH is also
calling for cooling, power flows through thermostat
8
Figure 16.)
or
Figure 13 or Figure 15