Fan Performance 48Tf006 — Horizontal Discharge Units, Alternate Motor - Carrier 48TF004-007 Installation, Start-Up And Service Instructions Manual

Single-package rooftop heating/cooling units
Table of Contents

Advertisement

Table 26 — Fan Performance 48TF006 — Horizontal Discharge Units, Alternate Motor
48TF006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)*
Airflow
0.1
(Cfm)
Rpm
Bhp
Watts
1500
730
0.34
357
1600
770
0.40
420
1700
811
0.47
494
1800
852
0.55
578
1900
894
0.54
567
2000
936
0.74
778
978
0.85
893
2100
2200
1021
0.97
1019
2300
1064
1.10
1156
2400
1107
1.24
1303
2500
1150
1.39
1460
48TF006 (5 TONS) — ALTERNATE MOTOR (BELT DRIVE)* (cont)
Airflow
1.2
(Cfm)
Rpm
Bhp
Watts
1500
1221
1.17
1229
1600
1252
1.27
1334
1700
1278
1.37
1439
1800
1303
1.48
1555
1900
1330
1.59
1671
2000
1362
1.73
1818
2100
1393
1.87
1965
2200
1423
2.02
2122
2300
1454
2.18
2291
2400
1485
2.36
2480
2500
1518
2.55
2679
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range is 900 to 1300 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
External Static Pressure (in. wg)
0.2
0.4
Rpm
Bhp
Watts
Rpm
Bhp
789
0.40
420
896
0.53
826
0.46
483
931
0.61
865
0.54
567
966
0.69
905
0.62
651
1002
0.78
945
0.72
757
1037
0.88
984
0.82
862
1072
0.98
1024
0.93
977
1108
1.10
1064
1.05
1103
1145
1.22
1104
1.18
1240
1183
1.36
1145
1.32
1387
1222
1.45
1186
1.48
1555
1262
1.68
External Static Pressure (in. wg)
1.4
1.6
Rpm
Bhp
Watts
Rpm
Bhp
1256
1.30
1366
1283
1.32
1311
1.45
1524
1340
1.58
1345
1.57
1650
1397
1.76
1371
1.69
1776
1433
1.90
1396
1.80
1902
1460
2.03
1422
1.94
2038
1485
2.16
1452
2.08
2185
1510
2.31
1483
2.24
2354
1538
2.46
1515
2.41
2532
1571
2.64
1544
2.59
2721
1604
2.84
1574
2.78
2905
1633
3.03
0.6
Watts
Rpm
Bhp
Watts
Rpm
557
990
0.67
704
1072
641
1020
0.75
788
1101
725
1051
0.84
883
1133
820
1084
0.93
977
1163
925
1119
1.04
1093
1194
1030
1154
1.16
1219
1226
1156
1192
1.29
1355
1259
1282
1225
1.43
1503
1294
1429
1260
1.57
1650
1330
1524
1296
1.73
1818
1365
1765
1331
1.89
1986
1400
1.8
Watts
Rpm
Bhp
Watts
1387
1303
1.22
1282
1660
1330
1.61
1692
1849
1424
1.89
1986
1996
1480
2.09
2196
2133
1517
2.25
2364
2270
1544
2.40
2522
2427
1570
2.55
2674
2585
1594
2.71
2821
2758
1623
2.88
2976
2947
1657
3.07
3152
3134
1692
3.28
3345
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 1.30 for single-phase units and 2.40
for 3-phase units and the maximum continuous watts are 2120.
Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
32
0.8
1.0
Bhp
Watts
Rpm
Bhp
Watts
0.83
872
1153
1.00
1051
0.91
956
1178
1.09
1145
1.01
1061
1205
1.18
1240
1.10
1156
1235
1.29
1355
1.21
1271
1266
1.40
1471
1.33
1397
1297
1.53
1608
1.47
1545
1327
1.66
1744
1.62
1702
1359
1.80
1902
1.78
1870
1392
1.97
2070
1.94
2038
1426
2.15
2259
2.12
2227
1461
2.34
2459