Base Unit Dimensions - Carrier 48TF004-007 Installation, Start-Up And Service Instructions Manual

Single-package rooftop heating/cooling units
Table of Contents

Advertisement

STD UNIT
WEIGHT
UNIT
Lbs
Kg
48TFN,TFM,TFF,TFE004
460
209
48TFN,TFM,TFL,TFF,TFE,TFD005
470
213
48TFN,TFM,TFL,TFF,TFE,TFD006
490
222
48TFF,TFE,TFD007
565
256
CONNECTION SIZES
3
A
1
/
Dia. [35] Field Power Supply Hole
8
2 Dia. [51] Power Supply Knockout
B
1
C
2
/
Dia. [64] Power Supply Knockout
2
7
D
/
Dia. [22] Field Control Wiring Hole
8
E
3
/
-14 NPT Condensate Drain
4
1
F
/
-14 NPT Gas Connection
2
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Center of Gravity.
3.
Direction of Airflow.
4. On vertical discharge units, ductwork to be attached to accessory
roof curb only. For horizontal discharge units, field-supplied flanges
should be attached to horizontal discharge openings, and all duct-
work should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb)
1 inch. Bottom of base rail to combustible surfaces (when not
using curb) 0 inches.
c. Condenser coil for proper airflow, 36 in. one side, 12 in. the other.
The side getting the greater clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electri-
cal Code).
f. Between unit and ungrounded surfaces, control box side, 36 in.
per NEC.
g. Between unit and block or concrete walls and other grounded sur-
faces, control box side, 42 in. per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and com-
bustion side as stated in Note 5a, b, and c, a removable fence or bar-
ricade requires no clearance.
7. Units may be installed on combustible floors made from wood or
Class A, B, or C roof covering material if set on base rail.
8. The vertical center of gravity is 1 -6 [457] up from the bottom of the
base rail.
DURABLADE
ECONOMI$ER
ECONOMIZER WEIGHT
WEIGHT
CORNER WEIGHT
Lbs
Kg
Lbs
Kg
Lbs
140
142
34
15.4
47
21.3
150
165
Fig. 6 — Base Unit Dimensions
(A)
(B)
(C)
CORNER WEIGHT
CORNER WEIGHT
Kg
Lbs
Kg
Lbs
Kg
63.5
105
47.6
159
72.1
64.4
106
48.1
162
73.5
68.0
115
52.2
160
72.6
74.8
136
61.7
200
90.7
(D)
"A"
THESE HOLES REQ'D FOR USE
CORNER WEIGHT
PANEL
WITH ACCESSORY PACKAGES —
LENGTH
Lbs
Kg
CRBTMPWR001A00, 3A00 (
56
25.4
1 -10
3
/
[568.0]
8
3
THREADED
60
27.2
1 -10
/
[568.0]
8
CONDUIT
3
65
29.5
1 -0
/
[315.0]
8
SIZE
64
29.0
1 -0
3
/
[315.0]
8
1
/
2
BOTTOM POWER CHART,
1
3
/
,
/
)
2
4
REQ'D HOLE
WIRE
SIZES
USE
(Max.)
1
7
/
24 V
/
[22.2]
2
8
3
1
/
Power
1
/
[28.4]
4
8
FPT
Gas
1
1
/
[31.8]
4